NTP display offset
The offset of the NTP display is the time difference between the actual local time and the
UTC time (UTC = Universal Time Coordinated) in minutes.
This can be used to indicate the actual local time. A value from -1440 min (-1 day) to 1440
min (+1 day) can be entered.
Substitute value
In the event of a bus failure, the outputs of the soft starters are controlled by a corresponding
substitute process image.
Parameters disabled CPU/Master
1. Navigate in the menu of the 3RW44 to the "Fieldbus interface > On" menu command (see
Activation of the fieldbus interface (Page 32))
2. Use the arrow keys to navigate to "Parameters disabled CPU/Master".
3. Press "OK".
4. Select "On" or "Off".
Note
If the "Parameters disabled CPU/Master" parameter is "Off" (basic factory setting), the
parameters set on the soft starter are overwritten with the values stored in the GSD file or
OM during bus startup. If this is not desired, the parameter must be set to "On".
5. Confirm the selection with the "OK" key.
PROFINET Communication Module for SIRIUS Soft Starter 3RW44
Manual, 12/2013, A5E31996495002A/RS-AA/001
6.3 Parameter settings in the soft starter under Fieldbus
Commissioning
41