Error Types - Siemens SIRIUS PROFINET Manual

Industrial controls, communication module for soft starter
Table of Contents

Advertisement

Triggering of a diagnostics interrupt
When an incoming or outgoing event (e.g., a wire break) is registered, the module triggers a
diagnostics interrupt Diagnostics interrupt" is set.
The CPU interrupts the user program and executes the diagnostics block OB 82. The
interrupt triggering event will be logged in the start information of OB 82.
7.6.2.2

Error types

The diagnostics alarm is signaled on channel 0.
Error
Error type
no.
F1
00001:
Short-circuit
F4
00100:
Overload
F5
00101:
Overtemperature
F6
00110:
Wire break
F7
00111:
High limit exceeded
F8
01000:
Low limit exceeded
F9
01001:
Error
F16
10000:
Parameter assignment error
F17
10001:
No sensor or load voltage
PROFINET Communication Module for SIRIUS Soft Starter 3RW44
Manual, 12/2013, A5E31996495002A/RS-AA/001
Meaning / cause
Short-circuit of the temperature sensor
Overload of the temperature sensor
Overload of the thermal motor model
Overload of the contact block
Wire break of the temperature sensor
Current limit exceeded
Current limit undershot
Internal error/device error
Contact block defective
Incorrect parameter value
Electronics supply voltage too low
No contact block supply voltage
No main power
Functions
7.6 Diagnostic functions
Delete alarm bit /
acknowledgement
Alarm bit is automatically
deleted when the cause of
tripping has been eliminated
and acknowledged with "Trip
Reset".
Alarm bit is updated
continually.
Alarm bit is automatically
deleted when the cause of
tripping has been eliminated
and acknowledged with "Trip
Reset".
Alarm bit is updated
continually.
Alarm bit can be deleted
when the cause of the error
has been eliminated by
Switching the supply
voltage On and Off
"Restart" command if
possible
Alarm bit is always deleted
when acknowledged with
"Trip Reset".
Alarm bit is deleted when the
cause of tripping has been
eliminated or automatically
acknowledged.
61