Object
Byte
Meaning
Bit
No.
173
122
Stopping torque
123
Reserved = 0
124
Reserved = 0
119
125
Motor thermal capacity
126 ...
Reserved = 0
129
178
130
Dynamic braking torque
43
131
Slow speed factor right
198
132
Slow speed factor left
44
133
Slow speed torque right
199
134
Slow speed torque left
135 ...
Reserved = 0
137
1) This parameter is evaluated in the soft starter without the digits after the decimal point.
Dependencies
● Maximum current limit > Minimum current limit
● DC braking can only be selected if an output has the "DC braking contactor" function
assigned.
● Maximum starting time ≥ Starting time
● Limiting torque > Start torque
PROFINET Communication Module for SIRIUS Soft Starter 3RW44
Manual, 12/2013, A5E31996495002A/RS-AA/001
A.1 Data formats and data records
Only in
Value range/ [coding]
data
record
131
10 ... 100 % [2 ... 20]
1 ... 100 % [1 ... 100]
20 ... 100 % [4 ... 20]
3 ... 21 [3 ... 21]
3 ... 21 [3 ... 21]
20 ... 100 % [4 ... 20]
20 ... 100 % [4 ... 20]
Appendix
Factor
5 %
1 %
5 %
1
1
5 %
5 %
101