Commissioning

6.2 Activation of the PROFINET communication module via software

6.2
Activation of the PROFINET communication module via software
You activate the PROFINET communication module ("Fieldbus" device function) using the
"Soft Starter ES 2007 + SP5" software.
Note
The PROFINET communication module only works with 3RW44 devices with product
version "E12" and firmware version V1.11.0 or higher.
Note
Following activation of the communication module, the default control priority automatically
switches from the inputs to "SPS über Feldbus PROFINET" (PLC via PROFINET fieldbus)
(automatic mode).
If an input with the "Manual operation local" function is active, the control priority does not
change.
To activate the PROFINET communication module, follow these steps:
1. Connect the 3RW44 soft starter via the interface cable to a PC on which the "Soft Starter
ES 2007 + SP5" (or higher) software is installed.
2. Start the "Soft Starter ES 2007" software.
3. Select "Switching Device > Open Online" in the menu.
4. Select the "Local device interface" option in the "Open Online" dialog and select the
desired COM port under "Interface".
5. Click "OK".
6. Select "Device configuration" on the left side of the window.
7. Make sure that the firmware version of the connected 3RW44 soft starter is V1.11 or
higher.
34
PROFINET Communication Module for SIRIUS Soft Starter 3RW44
Manual, 12/2013, A5E31996495002A/RS-AA/001