Appendix
A.1 Data formats and data records
A.1.14

Data record 96 - Read maximum pointer

Byte
Meaning
Bit
4
Phase current I
5
Phase current I
6
Phase current I
7
Reserved = 0
8
Phase current I
9
Phase current I
10
Phase current I
11
Reserved = 0
12 ... 13
Maximum tripping current I
14 ... 15
Number of motor overload trips
16 ... 19
Maximum tripping current I
20 ... 23
Phase current I
24 ... 27
Phase current I
28 ... 31
Phase current I
32 ... 35
Phase current I
36 ... 39
Phase current I
40 ... 43
Phase current I
44 ... 45
Line-to-line voltage U
46 ... 47
Line-to-line voltage U
48 ... 49
Line-to-line voltage U
50 ... 51
Line-to-line voltage U
52 ... 53
Line-to-line voltage U
54 ... 55
Line-to-line voltage U
56 ... 57
Electronics supply voltage U
58 ... 59
Electronics supply voltage U
60
Maximum cooling temperature
61
Maximum contact black heating
62
Minimum line frequency
63
Maximum line frequency
64 ... 67
Operating hours -
motor current = 18 ... 49.9 % x l
68 ... 71
Operating hours -
motor current = 50 ... 89.9 % x l
72 ... 75
Operating hours -
motor current = 90 ... 119.9 % x l
76 ... 79
Operating hours -
motor current = 120 ... 1000 % x l
80 ... 83
Operating hours device
84 ... 85
Reserved = 0
96
(%)
L1 min
(%)
L2 min
(%)
L3 min
(%)
L1 max
(%)
L2 max
(%)
L3 max
(%)
A max
(rms)
A max
(rms)
L1 min
(rms)
L2 min
(rms)
L3 min
(rms)
L1 max
(rms)
L2 max
(rms)
L3 max
(rms)
L1 - L2min
(rms)
L2 - L3min
(rms)
L3 - L1min
(rms)
L1 - L2max
(rms)
L2 - L3max
(rms)
L3 - L1max
(rms)
NS min
(rms)
NS max
e
e
e
e
Value range/ [coding]
0 ... 797 % / [0 ... 255]
0 ... 797 % / [0 ... 255]
0 ... 797 % / [0 ... 255]
0 ... 797 % / [0 ... 255]
0 ... 797 % / [0 ... 255]
0 ... 797 % / [0 ... 255]
0 ... 1000 % / [0 ... 320]
0 ... 65 535 / [0 ... 65 535]
0 ... 20 000 A / [0 ... 2 000 000]
0 ... 20 000 A / [0 ... 2 000 000]
0 ... 20 000 A / [0 ... 2 000 000]
0 ... 20 000 A / [0 ... 2 000 000]
0 ... 20 000 A / [0 ... 2 000 000]
0 ... 20 000 A / [0 ... 2 000 000]
0 ... 20 000 A / [0 ... 2 000 000]
0 ... 1500 V / [0 ... 15 000]
0 ... 1500 V / [0 ... 15 000]
0 ... 1500 V / [0 ... 15 000]
0 ... 1500 V / [0 ... 15 000]
0 ... 1500 V / [0 ... 15 000]
0 ... 1500 V / [0 ... 15 000]
0 ... 1500 V / [0 ... 15 000]
0 ... 1500 V / [0 ... 15 000]
1 ... -40 °C / [-40 ... 127]
0 ... 250 % / [0 ... 250]
0 ... 100 Hz / [0 ... 200]
0 ... 100 Hz / [0 ... 200]
0 ... 2
-1 s / [0 ... 2
-1]
32
32
0 ... 2
-1 s [0 ... 2
-1]
32
32
0 ... 2
-1 s [0 ... 2
-1]
32
32
0 ... 2
-1 s / [0 ... 2
-1]
32
32
PROFINET Communication Module for SIRIUS Soft Starter 3RW44
Increment
Comment
3,125 %
In bypass operation
3,125 %
In bypass operation
3,125 %
In bypass operation
In bypass operation
3,125 %
In bypass operation
3,125 %
In bypass operation
3,125 %
In bypass operation
3,125 %
1
0.01 A
0.01 A
In bypass operation
0.01 A
In bypass operation
0.01 A
In bypass operation
0.01 A
In bypass operation
0.01 A
In bypass operation
0.01 A
In bypass operation
0.1 V
Reset to 0 in the
event of phase failure
0.1 V
or switch-off of main
0.1 V
voltage.
0.1 V
0.1 V
0.1 V
0.1 V
Reset to zero at
"Power on"
0.1 V
1 °C
1 %
0.5 Hz
For line or phase loss
0.5 Hz
1 s
1 s
1 s
1 s
1 s
Manual, 12/2013, A5E31996495002A/RS-AA/001