Configuring/assigning parameters
5.2 Configuring the properties of 3RW44 PN as IO device
Possibilities for this are:
● The IO controller assigns the IP parameters to the IO device.
Note
Deleting IP parameters
IP parameters assigned by the IO controller are not stored retentively in the device, i.e.,
they are deleted when the supply voltage is switched off.
● The IP parameters are configured with the "Soft Starter ES 2007" software and
transferred to the device. In this case, the "Overwrite IP parameters in device" parameter
under "PROFINET Parameters > IP-Parameters" must be activated.
Note
Transferring the device parameters
It is always possible to transfer the device parameters via the local device interface.
If the PROFINET IO device name or the IP address has already been configured in a
different way, the device parameters can also be transferred via PROFINET.
Note
Assigning the IP parameters
The IP parameters can be transferred to the selected device using the following functions
of the "Soft Starter ES 2007" software.
• Select "Target System > Edit Ethernet Node". This function is not identical to the
• Select "PROFINET Parameters > IP-Parameters". The "Overwrite IP parameters in
Note
Restarting the communication interface
Any change of the IP parameters using the "PROFINET Parameters" dialog box of "Soft
Starter ES 2007" requires a restart of the communication interface.
A new start of the communication interface interrupts all Ethernet and PROFINET links
and reestablishes them afterward.
● Input of IP address, subnet mask, router address via the display of the 3RW44 (for
procedure, see Parameter settings in the soft starter under Fieldbus (Page 36)).
Saving the parameters retentively
In order to save the modified parameters retentively, select "Save settings" in the menu of
the 3RW44 soft starter.
30
parameter assignment of the IP parameters using the "PROFINET Parameters" dialog
box.
device" parameter must be activated.
PROFINET Communication Module for SIRIUS Soft Starter 3RW44