SIRIUS
3RW44
Soft starter
System manual
Order No.: 3ZX1012-0RW44-1AC1
Issue 06/2005
GWA 4NEB 535 2195-02 DS 01
Table of contents
Important notes
Introduction
Configuration instructions
Installation, connection and
branch construction
Display, controls and device
interfaces
Commissioning
Device functions
Diagnostics and messages
Circuit examples
General technical data
Appendix
Index
1
2
3
4
5
6
7
8
9

Advertisement

Table of Contents
loading

Summary of Contents for Siemens Sirius 3RW44

  • Page 1 Table of contents Important notes Introduction Configuration instructions SIRIUS Installation, connection and branch construction 3RW44 Display, controls and device interfaces Soft starter Commissioning System manual Device functions Diagnostics and messages Circuit examples General technical data Appendix Index Order No.: 3ZX1012-0RW44-1AC1 Issue 06/2005 GWA 4NEB 535 2195-02 DS 01...
  • Page 3 Trademarks All names carrying the industrial property mark ® are registered trademarks of Siemens AG. The other designations in this publication may be trademarks whose use by third parties for their own purposes may infringe the rights of the owners.
  • Page 5: Table Of Contents

    1.1.2 Operating mode of the SIRIUS 3RW44 electronic soft starter ......1-4 Application and use ............. 1-7 Boundary conditions for storage and operation .
  • Page 6 3RW44 in a standard circuit with line contactor and control via PLC ......8-3 SIRIUS 3RW44 soft starter...
  • Page 7 Index ..............Index-1 SIRIUS 3RW44 soft starter...
  • Page 8 Table of contents SIEMENS SIRIUS 3RW44 soft starter GWA 4NEB 535 2195-02 DS 01...
  • Page 9: Important Notes

    Definitions If the short form 3RW44 is used in the text, it refers to the SIRIUS 3RW44 soft starter. Standards and approvals The SIRIUS 3RW44 soft starter complies to the IEC/EN 60947-4-2 standard.
  • Page 10: Issue

    SIEMENS. SIEMENS can also not assume liability for recommendations given or implied by the following description. No new guarantee/warranty or liability claims in excess of the general terms and conditions of SIEMENS can be deduced from the following description. Handling...
  • Page 11: Introduction

    Physical basics of the 3-phase asynchronous motor and mode of operation of the soft starter 1.1.1 3-phase asynchronous motor 1.1.2 Operating mode of the SIRIUS 3RW44 electronic soft starter Application and use Boundary conditions for storage and operation SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 12: Physical Basics Of The 3-Phase Asynchronous Motor And Mode Of Operation Of The Soft Starter

    Disadvantages This results in the following disadvantages • Higher load on mechanical parts of the machine • Higher costs because of application wear and maintenance SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 13 Typical start torque behavior of a 3-phase asynchronous motor Solution The current and torque behavior during start-up can be optimally adapted to the requirement of the application using the SIRIUS 3RW44 electronic soft starter. SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 14: Operating Mode Of The Sirius 3Rw44 Electronic Soft Starter

    Introduction 1.1.2 Operating mode of the SIRIUS 3RW44 electronic soft starter The 3RW44 soft starter has two antiparallel thyristors in each of the phases. There is one thyristor for the positive and one thyristor for the negative half wave. Using phase angle control and various control methods, the r.m.s. value of the motor voltage is increased from a definable start voltage or start torque to the motor rated voltage within a selectable starting time.
  • Page 15 Soft start Sanftstart torque-controlled Drehmomentgeregelt Load e.g. pump Last (z. B. Pumpe) Fig. 1-4: Reduced torque behavior of the 3-phase asynchronous motor during start-up with SIRIUS soft starter 3RW44 SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 16 The following graph illustrates the mode of operation of the 3RW44 soft starter: L1 -L3 ϕ t α α α Fig. 1-5: Phase angle control and schematic layout of a soft starter with internal bypass contacts SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 17: Application And Use

    • Jerk-free braking Centrifugal pumps, reciprocating pumps: • Water hammering is avoided • Increased service life of the tubing Stirrers, mixers: • Reduced starting current Fans: • Reduced stress on transmissions and V-belts SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 18: Boundary Conditions For Storage And Operation

    Permissible relative air humidity 10 ... 95 % Maximum permissible installation 3000 m, from 1000 m with derating height Caution Please ensure that no liquid, dust or conductive parts enter the soft starter! SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 19: Configuration Instructions

    Example applications for normal starting (Class 10) 2.2.2 Example applications for heavy starting (Class 20) 2.2.3 Example applications for heaviest starting (Class 30) On-time and switching frequency Installation height and ambient temperature Factory setting SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 20: Configuration

    Softstarter ES smart software and with an operating and monitoring module. 2.1.2 Win-SOFTSTARTER selection and simulation program This software allows all SIEMENS soft starters to be simulated and selected using various parameters such as network conditions, motor data, load data, special application requirements, etc.
  • Page 21: Normal Or Heavy Starting

    Technical data power component. If deviations from these data occur, it may be necessary to overdimension the soft starter. Using the Win-SOFTSTARTER selection and simulation program from SIEMENS, you can enter your application data and requirements, and it will determine the optimum soft starter dimensions for your application (refer to Section 9.3.8 Accessories Software).
  • Page 22: Example Applications For Heaviest Starting (Class 30)

    Soft starter dimensioning should, if required, be verified with the help of the Win-SOFTSTARTER program or via the Technical Assistance in Section Important notes . SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 23: On-Time And Switching Frequency

    Idle time [s] The following graphic illustrates the procedure. Fig. 2-1: On-time OT Switching frequency To prevent thermal overloading of the devices, the maximum permissible switching frequency must be adhered under all circumstances. SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 24: Installation Height And Ambient Temperature

    (refer to Section 9.3.2 Technical data power component). SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 25: Factory Setting

    Factory setting We recommend you apply the factory settings (default settings) • in the event of faulty parameterization • if SIRIUS 3RW44 soft starters that have already been parameterized are to be used further in other systems. Notice If this is not done, drives may start running because of the present parameterization.
  • Page 26 Configuration instructions SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 27: Installation, Connection And Branch Layout

    Protection of the soft starter against short circuits Capacitors for power factor improvement 3-10 Electrical connection 3-10 3.5.1 Control and auxiliary current connection 3-10 3.5.2 Main current connection 3-11 3.5.3 Conductor cross-sections 3-12 SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 28: Installing The Soft Starter

    Operation of the soft starter produces waste heat (heat loss) (refer to Chapter 9 General technical data). Caution Ensure sufficient cooling where the unit is installed to prevent the switching device from overheating. SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 29: Mounting Dimensions And Clearances

    [≥ 3 in] Fig. 3-2: Clearance with other devices Notice Cater for sufficient clearance to ensure that air can freely circulate for cooling. The unit is ventilated from bottom to top. SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 30: Branch Layout

    When working on the branch, it must be disconnected using a disconnector (open isolating gap, e.g. with a repair switch)! SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 31: Soft Starters In Standard Circuits

    Installation, connection and branch layout 3.2.2 Soft starters in standard circuits The SIRIUS 3RW44 soft starter is connected in the motor branch between the disconnector or circuit-breaker and the motor. The 3RW44 soft starter automatically detects the connection type of the soft starter so this does not have to be explicitly set on the device.
  • Page 32: Soft Starter In Inside Delta Circuits

    Fig. 3-4: Name plate of a 22 kW motor Here the SIRIUS 3RW44 soft starter can be dimensioned to match the current flowing in the motor section (58 % of the conductor current) by connecting it in the delta winding of the motor. This requires at least 6 motor lines.
  • Page 33 Otherwise the soft starter would not recognize the current circuit version (standard circuit or inside delta circuit) and output an error message: "load phases 1-3 missing". SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 34: Soft Starter With Contactor Disconnector (Main Contactor)

    Otherwise the soft starter would not recognize the current circuit version (standard circuit or inside delta circuit) and output an error message: "load phases 1-3 missing". SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 35: Protection Of The Soft Starter Against Short Circuits

    To suit this purpose, special semiconductor fuses, e.g. SITOR fuses from SIEMENS, must be used. (Refer to Chapter 9.3 Technical data for the fuse assignment) 3/N/PE~ 50 Hz 400 V Fig.
  • Page 36: Capacitors For Power Factor Improvement

    Electrical connection 3.5.1 Control and auxiliary current connection The SIRIUS 3RW44 soft starter is supplied with two different connection types: • Screw-type connection • Spring-loaded terminals Two control voltage versions are available: •...
  • Page 37: Main Current Connection

    NC NO A1, A2, PE, L+, L-, IN1, IN2, IN3, IN4, T1, T2, 13, 14, 23, 24, 33, 34, 95, 96, 98: Main/auxiliary circuit L1/L2/L3, T1/T2/T3: Main circuit Fig. 3-8: Connections SIRIUS 3RW44 manual 3-11 GWA 4NEB 535 2195-02 DS 01...
  • Page 38: Conductor Cross-Sections

    ≤ 17 mm b ≤ 25 mm 2 x AWG 10 ... 1/0 1 x AWG 10 ... 2/0 4 ... 6 Nm min 22 36 ... 53 lb·in SIRIUS 3RW44 manual 3-12 GWA 4NEB 535 2195-02 DS 01...
  • Page 39: Display, Controls And Device Interfaces

    Display, controls and device interfaces Display, controls and device interfaces Chapter Subject Page Display and controls Device interfaces 4.2.1 Local device interface 4.2.2 Profibus interface (optional) SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 40: Display And Controls

    The up/down keys are used to navigate through the menu items or to change number values in the settings menu item. The ESC key is used to quit the current menu item and to jump back to the higher-level menu item. SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 41: Device Interfaces

    "Accessories" , Software) using a PC and connecting cables. 4.2.2 Profibus interface (optional) The SIRIUS 3RW44 soft starter can be fitted with an optional Profibus module (only with product delivery after 12/05). The soft starter can be connected to the Profibus, operated and parameterized via the interface.
  • Page 42 Display, controls and device interfaces SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 43: Commissioning

    5.4.13 Saving options 5-25 Other device functions 5-28 5.5.1 Measured value display 5-28 5.5.2 Status display 5-29 5.5.3 Motor control (assign control priority) 5-30 5.5.4 Safety (define user level, parameterization protection) 5-30 SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 44: Menu Structure, Navigation, Changing Parameters

    Rated operating Select Select torque Parameter Select Select 100 Nm set 3 Change Stopping Safety Select Select settings Rated operating speed Select Select Select Select 1500 Inputs Change Fig. 5-1: Menu structure SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 45: Changing Parameters: For Example Motor Data

    29.0 A Change Rated operating current Ie 29.0 A Save Rated operating current Ie 28.9 A Save Rated operating current Ie 28.9 A Change Fig. 5-2: Changing values, e.g. adjusting motor data SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 46: Switching On For The First Time

    (refer to Chapter 2.5 Factory setting). This overwrites all settings made up until that point. SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 47 Save Starting time 10 s Save Current limit value 1mpe 450 % Save Function call 1mpe Save settings Save settings 1mpe Run? SIEMENS 1mpe 3RW44 Menu Fig. 5-3: Quick start menu SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 48: User-Specific Commissioning

    In order to permanently save the settings made in the soft starter, you must save the data as described in Chapter 5.3.1 “Settings” main menu item and Chapter 5.4.13 Saving options. SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 49: Settings" Main Menu Item

    2 Select Parameter set 3 Select Inputs Select Outputs Select Motor protection Select Display Select Response to ... Select Name Select Saving options Select Fig. 5-4: Main menu item settings SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 50: Making Settings In The Selected Parameter Set

    Making settings in the selected parameter set 5.4.1 Select parameter set Parameter set 1 Select Motor 1 Select Starting settings Select Stopping settings Select Slow-speed parameters Select Current limit values Select Fig. 5-5: Select parameter set SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 51: Entering Motor Data

    (e.g. for testing purposes), these rated data must be adapted to this new motor. If 0 Nm is entered as rated torque, the value is automatically calculated once by the soft starter. SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 52: Determining The Starting Mode

    M+ current lim. Select Starting mode Torque control M+ current lim. 5 Direct Select Starting mode M+ current lim. Direct 6 Motor heating Select Fig. 5-7: Determining the starting mode SIRIUS 3RW44 manual 5-10 GWA 4NEB 535 2195-02 DS 01...
  • Page 53 Change Time (t) Breakaway time Breakaway time 0 ... 2000 ms Starting time 100 % Voltage at the motor 0 ms Maximum starting time Change 4_1_Menü_Startart_Spannungsrampe.wmf Fig. 5-8: Voltage ramp SIRIUS 3RW44 manual 5-11 GWA 4NEB 535 2195-02 DS 01...
  • Page 54 Breakaway time starting mode, in this 0 ... 2000 ms case voltage ramp 0 ms e Motor Change Motor speed e Motor 4_2_Menü_Startart_Spannungsrampe_mit_Strombegrenzung.wmf Fig. 5-9: Voltage ramp and current limiting SIRIUS 3RW44 manual 5-12 GWA 4NEB 535 2195-02 DS 01...
  • Page 55 Direct on-line starting (maximum torque to be generated) Breakaway voltage 4_3_Drehmomentrampe.wmf 40 ... 100 % 80 % Change Breakaway time 0 ... 2000 ms 0 ms Change Fig. 5-10: Torque control SIRIUS 3RW44 manual 5-13 GWA 4NEB 535 2195-02 DS 01...
  • Page 56 Breakaway time starting mode, in this 0 ... 2000 ms case torque control 0 ms e Motor Change Motor speed e Motor 4_4_Drehmomentrampe_mit_Strombegrenzung.wmf Fig. 5-11: Torque control with current limiting SIRIUS 3RW44 manual 5-14 GWA 4NEB 535 2195-02 DS 01...
  • Page 57 Motor speed 4_6_Menü_Startart_Direktstart_Strom.wmf Fig. 5-12: Direct on-line starting Starting mode: motor heating Starting settings Select Starting mode Motor heating Change Motor heating capacity 20 % Change Fig. 5-13: Motor heating SIRIUS 3RW44 manual 5-15 GWA 4NEB 535 2195-02 DS 01...
  • Page 58: Determining The Stopping Mode

    DC braking 5 Comb. braking Select 4_7_Auslaufart_allgemein.wmf Fig. 5-14: Determining the stopping mode Stopping mode: coasting down Stopping settings Select Stopping mode Coasting down Change Fig. 5-15: Stopping mode: coasting down SIRIUS 3RW44 manual 5-16 GWA 4NEB 535 2195-02 DS 01...
  • Page 59 0 ... 360 s 10 s Stopping torque Change Stopping torque 10 ... 100 % Time 40.0 % Stopping time Change Stop command soft starter 4_8_Menü_Auslaufart_Drehmomentregelung_Pumpenauslauf.wmf Fig. 5-17: Stopping mode: pump stop SIRIUS 3RW44 manual 5-17 GWA 4NEB 535 2195-02 DS 01...
  • Page 60 20 ... 100 % 50 % Change Dynamic braking to rque DC braking torque Motor braking to rque 20 ... 100 % 50 % Change 4_10_Menue_AuslaufartKombiniertes_Bremsen (2).wmf Fig. 5-19: Combined braking SIRIUS 3RW44 manual 5-18 GWA 4NEB 535 2195-02 DS 01...
  • Page 61: Setting Slow Speed Parameters

    ... to Select Minimum cur- rent limit 19 ... 100 % Deactivated Change Maximum cur- rent limit 50 ... 150 % Deactivated Change Fig. 5-21: Determining current limits SIRIUS 3RW44 manual 5-19 GWA 4NEB 535 2195-02 DS 01...
  • Page 62: Parameterization Of The Inputs

    DC brake contactor No action Group warning Change Group error Device error Output 4 - Power on Action Ready to start Group error Change Fig. 5-23: Parameterization of the outputs SIRIUS 3RW44 manual 5-20 GWA 4NEB 535 2195-02 DS 01...
  • Page 63 Commissioning Status diagram of the outputs SIRIUS 3RW44 manual 5-21 GWA 4NEB 535 2195-02 DS 01...
  • Page 64: Selection Of Motor Protection Settings

    1 ... 100 s 20 s Change Protection ag. voltage failure Yes; no Change Temperature sensor Deactivated; Thermo click; PTC type A Deactivated Change Fig. 5-24: Selection of motor protection settings SIRIUS 3RW44 manual 5-22 GWA 4NEB 535 2195-02 DS 01...
  • Page 65: Selection Of Display Settings

    Change Contrast 50 % Change Lighting Change Reaction time keys 60 % Change Auto repeat 20 s Change Activity monitor- ing time Deactivated Change Fig. 5-25: Selection of display settings SIRIUS 3RW44 manual 5-23 GWA 4NEB 535 2195-02 DS 01...
  • Page 66: Determining The Protective Functions

    Earth fault Warning Change Fig. 5-26: Determining the protective functions 5.4.12Determining the names on the device display Name Select Name Pump Select Fig. 5-27: Determining the names on the device display SIRIUS 3RW44 manual 5-24 GWA 4NEB 535 2195-02 DS 01...
  • Page 67 Fig. 5-28: Determining the saving options Save settings Selected settings will be saved. Saving options Select Function call Save settings Function call Save settings Save settings Run? SIEMENS 3RW44 Menu Fig. 5-29: Save settings SIRIUS 3RW44 manual 5-25 GWA 4NEB 535 2195-02 DS 01...
  • Page 68: Saving Options

    Selected but not saved settings will be discarded and the previous settings will be restored. Saving options Select Function call Save settings Function call Restore settings Restore settings Run? SIEMENS 3RW44 Menu Fig. 5-30: Restoring settings SIRIUS 3RW44 manual 5-26 GWA 4NEB 535 2195-02 DS 01...
  • Page 69 (master reset). The quick-start menu must be executed once again. Saving options Select Function call Save settings Function call Restore settings Function call Factory setting Factory setting Run? SIEMENS 3RW44 Menu Fig. 5-31: Restoring factory settings SIRIUS 3RW44 manual 5-27 GWA 4NEB 535 2195-02 DS 01...
  • Page 70: Other Device Functions

    Supply voltage 230 V Standard Heatsink temperature 22 °C Standard Motor heat build-up Standard Remaining time for tripping 65540 s Standard Function call Switch off standard display Save settings Run? SIRIUS 3RW44 manual 5-28 GWA 4NEB 535 2195-02 DS 01...
  • Page 71: Status Display

    Parameter set 1 Select Type of connection Unknown/fault Select Direction of rotation Unknown Change Inputs 20 s Select Outputs Standard Select Order number 3RW4422-1BC44 Firmware information Select Fig. 5-32: Status display SIRIUS 3RW44 manual 5-29 GWA 4NEB 535 2195-02 DS 01...
  • Page 72: Motor Control (Assign Control Priority)

    5.5.4 Safety (define user level, parameterization protection) Safety Safety Select Select Enter user Enter user code code 1000 1001 Change Change User level User level Customer write Customer read only Select Select Fig. 5-34: Safety SIRIUS 3RW44 manual 5-30 GWA 4NEB 535 2195-02 DS 01...
  • Page 73: Device Functions

    Coasting down 6-11 6.3.2 Torque control and pump stop 6-12 6.3.3 DC braking / combined braking 6-13 Slow speed function 6-16 Current limit values 6-17 Motor protection functions 6-18 Inherent protection 6-22 SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 74: Various Parameter Sets

    • Starting Dahlander motors (variable-speed drive). • Starting an application with different load conditions (e.g. empty of full conveyor belt). • Separate starting of up to three drives with different run-up behavior (e.g. compressor and pump). SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 75: Starting Modes

    6.2.1 Voltage ramp The most simple type of soft start with the SIRIUS 3RW44 is achieved using a voltage ramp. The terminal voltage of the motor is increased from a parameterizable start voltage to line voltage within an adjustable starting time.
  • Page 76 For machines requiring a breakaway pulse (inverse load response, e.g. in mills or crushers), the breakaway pulse must be set as described in Section 6.2.3. The voltage ramp+current limiting (U+current limiting) starting mode is recommended for heavy starting. SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 77: Torque Control

    100 % of the line voltage. The internal bypass contacts will close and the thyristors are bridged. SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 78 6.2.3. The torque control+current limiting (M+current limiting) starting mode is recommended for heavy starting (refer to chapter 6.2.4 Current limiting in combination with voltage ramp or torque control starting mode). SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 79: Breakaway Pulse In Combination With Voltage Ramp Or Torque Control Starting Mode

    Direct on-line sta rting (maximum torque that can begenerated) Soft start Breakaway pulse combined with torque regulation orvoltage ramp Load (e. g. Crusher) Fig. 6-4: Function principle of breakaway pulse/torque control SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 80 Load machines with inverse torque behavior, e.g. crushers and mills. Notice A breakaway pulse that is too high may lead to the error message "current measurement range exceeded". To remedy this, use larger starter dimensions or a lower breakaway voltage. SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 81: Current Limiting In Combination With Voltage Ramp Or Torque Control Starting Mode

    Typical applications for current limiting Used in applications with large centrifugal mass (mass reactance) and hence the long starting times, e.g. large fans in order to lighten the load on the supply network. SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 82: Starting Mode: Direct On-Line

    This capacity should be chosen in such a way that the motor will not be damaged. Typical applications for motor heating Used e.g. in outdoor drives to minimize condensation inside the motor. SIRIUS 3RW44 manual 6-10 GWA 4NEB 535 2195-02 DS 01...
  • Page 83: Stopping Modes

    Stopping modes Different stopping functions can be selected thanks of the large numbers of applications for which the SIRIUS 3RW44 soft starter can be used. The motor stop can be set optimally according to application and deployment. If a start command is output while the motor is being stopped, this process is aborted and the motor is started up again using the specified starting mode.
  • Page 84: Torque Control And Pump Stop

    Fig. 6-7: Soft stop / pump stop Typical applications for soft stop / pump stop In pumps to prevent water hammer. In conveyor belts to prevent goods from toppling. SIRIUS 3RW44 manual 6-12 GWA 4NEB 535 2195-02 DS 01...
  • Page 85: Dc Braking / Combined Braking

    DC braking torque The height of the DC braking torque determines the brake force of the motor. If the motor accelerates again during DC braking, the dynamic braking torque must be increased. SIRIUS 3RW44 manual 6-13 GWA 4NEB 535 2195-02 DS 01...
  • Page 86 The optimum parameters must be adjusted on the machine under appropriate load conditions. DC braking torque The height of the DC braking torque determines the brake force of the motor. SIRIUS 3RW44 manual 6-14 GWA 4NEB 535 2195-02 DS 01...
  • Page 87 Auslaufzeit Stop Stoppbefehl Motor braking Motorbrems= command at torque moment Sanftstarter soft starter Fig. 6-9: DC braking Typical applications for DC braking Lathes (e.g. for tool changeovers) or disk saws. SIRIUS 3RW44 manual 6-15 GWA 4NEB 535 2195-02 DS 01...
  • Page 88: Slow Speed Function

    PS1/2/3" must be assigned to the other. Also refer to circuit proposal in Chapter 8.1.7. Directions of rotation: Right: rotation in line phase direction Left: rotation against line phase direction SIRIUS 3RW44 manual 6-16 GWA 4NEB 535 2195-02 DS 01...
  • Page 89: Current Limit Values

    Upper current limit The upper limit value can be used to determine increased power loss in the value application e.g. caused by storage damage. SIRIUS 3RW44 manual 6-17 GWA 4NEB 535 2195-02 DS 01...
  • Page 90: Motor Protection Functions

    Depending on the set tripping class (class setting) and protection parameters, a warning or a trip is generated when the characteristic curve is touched. SIRIUS 3RW44 manual 6-18 GWA 4NEB 535 2195-02 DS 01...
  • Page 91 > 50 %, otherwise it is set to 0 %. This enables frequent start procedures (inching). These frequent start procedures lead to tripping where motor protection acc. to IEC 60 947 is used, depending on class setting. SIRIUS 3RW44 manual 6-19 GWA 4NEB 535 2195-02 DS 01...
  • Page 92 When the control supply voltage returns, the trip condition of the thermal motor model before voltage failure will be restored. SIRIUS 3RW44 manual 6-20 GWA 4NEB 535 2195-02 DS 01...
  • Page 93 Two different types of measuring sensors are available for the evaluation. • PTC thermistors type A (“type A sensors”) • Thermo click The wiring and the sensors are checked for wire breaks or short circuits. SIRIUS 3RW44 manual 6-21 GWA 4NEB 535 2195-02 DS 01...
  • Page 94: Inherent Protection

    You can find the corresponding selection tables in Chapter 9.3.6 Branch component layout (standard circuit) and in Chapter 9.3.7 Branch component layout (inside delta circuit). SIRIUS 3RW44 manual 6-22 GWA 4NEB 535 2195-02 DS 01...
  • Page 95: Diagnostics And Messages

    Diagnostics and messages Diagnostics and messages Chapter Subject Page Diagnostics, messages 7.1.1 Status messages 7.1.2 Warnings and group errors 7.1.3 Device errors SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 96: Diagnostics, Messages

    Remedy: connect motor properly. Missing load phase T2 Motor phase T2 is not connected. Remedy: connect motor properly. Missing load phase T3 Motor phase T3 is not connected. Remedy: connect motor properly. SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 97 Remedy: check temperature sensor, or if none is connected: deactivate temperature sensor. Temperature sensor overload Temperature sensor at terminals T1/T2 has tripped, the motor is overheated. Remedy: wait until the motor has cooled down. SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 98: Device Errors

    The temperature sensor at the heatsink of the starter is defective. Notice It may occur that wrong error messages are output (e.g. phase failure L1, even though it is actually L2 that is missing). SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 99: Circuit Examples

    3RW44 in a standard circuit with soft start/stop and additional slow speed function in both directions of rotation with one parameter set 8.1.8 3RW 44 in a standard circuit with reversing operation via main contactors with one parameter set SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 100: Connection Examples For Main And Control Circuits

    3 / N / P E A C 4 0 0 V 400 V AC , 5 0 H z F 1 ' 1) For permissible main and control voltage values, refer to Technical Data, pages 9-7 to 9-10. SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 101: 3Rw44 In A Standard Circuit With Line Contactor And Control Via Plc

    This especially applies to motor protection tripping. For safety reasons it is recommended to integrate the group fault output (terminals 95 and 96) into the control. SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 102: 3Rw44 22 To 3Rw44 25

    9-15 for types. The "DC braking" function is recommended for applications with larger centrifugal masses (J > J load motor Output 2 must be switched over to "DC brake contactor". SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 103 Output 2 must be switched over to "DC brake contactor". 4) K4 auxiliary relay, e.g.: LZX:RT4A4T30 (230 V AC rated control supply voltage), LZX:RT4A4S15 (115 V AC rated control supply voltage). SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 104: 3Rw44 In An Inside Delta Circuit

    This especially applies to motor protection tripping. For safety reasons it is recommended to integrate the group fault output (terminals 95 and 96) into the control. SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 105: 3Rw44 In A Standard Circuit And Controlled Like A Contactor

    Circuit examples 8.1.6 3RW44 in a standard circuit and controlled like a contactor SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 106: 3Rw44 In A Standard Circuit With Soft Start/Stop And Additional Slow Speed Function In Both Directions Of Rotation With One Parameter Set

    Circuit examples 8.1.7 3RW44 in a standard circuit with soft start/stop and additional slow speed function in both directions of rotation with one parameter set SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 107: 3Rw 44 In A Standard Circuit With Reversing Operation Via Main Contactors With One Parameter Set

    Circuit examples 8.1.8 3RW 44 in a standard circuit with reversing operation via main contactors with one parameter SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 108 Circuit examples SIRIUS 3RW44 manual 8-10 GWA 4NEB 535 2195-02 DS 01...
  • Page 109: General Technical Data

    Branch component layout (inside delta circuit) 9-16 9.3.8 Accessories 9-17 Tripping characteristics 9-18 9.4.1 Motor protection tripping characteristics: 3RW44 with symmetry 9-18 9.4.2 Motor protection tripping characteristics: 3RW44 with asymmetry 9-18 Dimension drawings 9-19 SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 110: Menu Structure

    Order number Save settings Motor left PS3 ** Firmware information Restore settings Input 2 - Action [...] Version Factory setting Input 3 - Action [...] Date Input 4 - Action [...] SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 111 No. of starts output 1 No. of starts output 2 No. of starts output 3 No. of starts output 4 * Delivery version 2 ** Possible only in connection with slow speed SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 112: Transport And Storage Conditions

    ° Temperature from -40 C to +80 Atmospheric pressure from 700 to 1060 hPa (normal operation up to 1000 m, 3000 m with derating) Relative humidity from 10 to 95 % SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 113: Technical Data

    — — — — 3RW44 47-@BC@6 Spring-loaded terminals Order No. extension for connection method Screw-type terminals Order No. extension for rated control supply voltage U 115 V AC 230 V AC SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 114 3RW44 46-@BC@6 — — — 3RW44 47-@BC@6 Spring-loaded terminals Order No. extension for connection method Screw-type terminals Order No. extension for rated control supply voltage U 115 V AC 230 V AC SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 115: Technical Data Power Component

    2) For intermittent operation S4 with On Time OT = 70 %, T = 40 °C, individual vertical installation. The specified switching frequencies do not apply to automatic operation. 3) Maximum configurable motor rated current I , depending on the Class setting. SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 116 2) For intermittent operation S4 with On Time OT = 70 %, T = 40 °C, individual vertical installation. The specified switching frequencies do not apply to automatic operation. 3) Maximum configurable motor rated current I , depending on the Class setting. SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 117 2) For intermittent operation S4 with On Time OT = 70 %, T = 40 °C, individual vertical installation. The specified switching frequencies do not apply to automatic operation. 3) Maximum configurable motor rated current I , depending on the Class setting. SIRIUS 3RW44 manual GWA 4NEB 535 2195-02 DS 01...
  • Page 118: Technical Data Control Section

    Reset option after trip Manual/automatic Manual Pre-charge time min. 2 ... 30 Device protection functions Trip on Thermal overloading of the thyristors Reset option after trip Manual/automatic Manual Pre-charge time min. SIRIUS 3RW44 manual 9-10 GWA 4NEB 535 2195-02 DS 01...
  • Page 119 Current asymmetry exceeded Thermal motor model overload Prewarning limit exceeded • Motor heat build-up • Remaining time for tripping Bypass elements defective Line overvoltage Current limits exceeded Motor stalling - tripping SIRIUS 3RW44 manual 9-11 GWA 4NEB 535 2195-02 DS 01...
  • Page 120 Group error Device error Power on Ready to start Motor temperature sensor Deactivated Deactivated Thermo click PTC type A 1) Motor left parameter possible only in combination with slow speed mode. SIRIUS 3RW44 manual 9-12 GWA 4NEB 535 2195-02 DS 01...
  • Page 121: Conductor Cross-Sections

    2) When connecting cable lugs acc. to DIN 46234 from a conductor with a cross-section of 240 mm² as well as DIN 46235 from a conductor cross-section of 185 mm², the 3RT19 66-4EA1 terminal cover is required to ensure phase clearance. SIRIUS 3RW44 manual 9-13...
  • Page 122: Electromagnetic Compatibility

    Class A limit value at 30 ... 1000 MHz Radio interference voltage EN 55011 Class A limit value at 0.15 ... 30 MHz Is a radio interference suppression filter required? Radio interference suppression level A (industrial applications) None SIRIUS 3RW44 manual 9-14 GWA 4NEB 535 2195-02 DS 01...
  • Page 123: Branch Component Layout (Standard Circuit)

    2) Additional K4 auxiliary relay, for device type 3RW44 26 and larger: LZX:RT4A4T30 (3RW44 soft starter with 230 V AC rated control supply voltage), LZX:RT4A4S15 (3RW44 soft starter with 115 V AC rated control supply voltage). SIRIUS 3RW44 manual 9-15 GWA 4NEB 535 2195-02 DS 01...
  • Page 124: Branch Component Layout (Inside Delta Circuit)

    3RW44 44 3NE3 230-0B 3NE3 333 3RT10 76-6AP36 3RW44 45 3NE3 233 3NE3 336 3TF68 44-0CM7 3RW44 46 3NE3 333 3NE3 336 3TF68 44-0CM7 3RW44 47 3NE3 335 3NE3 338-8 3TF69 SIRIUS 3RW44 manual 9-16 GWA 4NEB 535 2195-02 DS 01...
  • Page 125: Accessories

    Type Fans Fans 3RW44 2. and 115 V AC 3RW49 36-8VX30 3RW44 3. 230 V AC 3RW49 36-8VX40 3RW44 4. 115 V AC 3RW49 47-8VX30 230 V AC 3RW49 47-8VX40 SIRIUS 3RW44 manual 9-17 GWA 4NEB 535 2195-02 DS 01...
  • Page 126: Tripping Characteristics

    Ie 9.4.2 Motor protection tripping characteristics: 3RW44 with asymmetry Class 5 Class 10 Class 15 1 50 Class 20 Class 30 1 00 1 ,0 1 0,0 x Ie SIRIUS 3RW44 manual 9-18 GWA 4NEB 535 2195-02 DS 01...
  • Page 127: Dimension Drawings

    General technical data Dimension drawings N S B 0 _ 0 1 4 9 3 Type/dim. (mm) 3RW44 2. M6, 10 Nm 3RW44 3. M6, 10 Nm 3RW44 4. M8, 15 Nm SIRIUS 3RW44 manual 9-19 GWA 4NEB 535 2195-02 DS 01...
  • Page 128 General technical data SIRIUS 3RW44 manual 9-20 GWA 4NEB 535 2195-02 DS 01...
  • Page 129: Index

    Main current connection 3-11 Covers for soft starters 9-17 Measured value display 5-28 Current asymmetry limit value 6-19 Menu structure 5-2, 9-2 Current limit value Messages Current limit values 5-19, 6-17 SIRIUS 3RW44 manual Index-1 GWA 4NEB 535 2195-02 DS 01...
  • Page 130 User-specific commissioning Reversed direction of rotation Reversing operation Run-up recognition 6-3, 6-5, 6-9, 6-10 Voltage ramp 5-11, 6-3, 6-4 Voltage ramp and current limiting 5-12 Safety 5-30 Saving options 5-25 Warnings SIRIUS 3RW44 manual Index-2 GWA 4NEB 535 2195-02 DS 01...
  • Page 131 Telephone 92220 Amberg, Germany Fax: 09621 / 80-3337 SIRIUS 3RW44 soft starter manual Have you noticed any errors while reading this manual? Please use this form to inform us about any errors. All complaints and suggestions for improvements are very welcome.
  • Page 132 GWA 4NEB 535 2195-02 DS01...