Table of Contents

Advertisement

Functions
7.6 Diagnostic functions
Error
Error type
no.
F24
11000:
Actuator tripping
F26
11010:
External error
7.6.3

Diagnostics and alarms

Warning
Error without restart
Error with restart
Alarm
Manual bus connection abort
No external start parameters received
PIO error
62
Meaning / cause
Tripping due to overload
Tripping due to zero current
Tripping due to asymmetry
Tripping due to ground fault
Sensor supply overload
Process image error
① ② ③
Cause / Solution
x
The connection to the PC was interrupted (in the case of the
controller via the "Soft Starter ES 2007" software, web client, or
OPC UA client).
Remedy:
Connect the PC and reassume the control priority.
x
Occurs only during operation with the PROFINET
communication module or PROFIBUS DP communication
module. Incorrect or impermissible parameter values have been
sent by the PLC.
Remedy:
The "Soft Starter ES 2007" software can be used to read out the
incorrect parameter and to change it to a permissible value in
the PLC.
x
PIO error (faulty process image of the outputs) appears in the
following cases:
If "Motor right" and "Motor left" have been selected
simultaneously (cause 1) or
If Bit 0 and Bit 1 have been set simultaneously via the PLC
parameter set
Remedy:
Automatically reset if "Motor right" and "Motor left" are
deactivated again (in response to cause 1) or
If a valid parameter set (PS 1 - 3) is set again (in response
to cause 2).
PROFINET Communication Module for SIRIUS Soft Starter 3RW44
Delete alarm bit /
acknowledgement
Alarm bit is always deleted
when acknowledged with
"Trip Reset".
Additional acknowledgment
in combination with another
error.
Alarm bit is always deleted
when acknowledged with
"Trip Reset".
Manual, 12/2013, A5E31996495002A/RS-AA/001