Object
Byte
Meaning
Bit
No.
167
51
Starting mode
0...3
168
51
Stopping mode
4...7
35
52 ... 53
Substitute value
54 ... 55
Reserved = 0
56
Reserved = 0
0...5
36
56
Group diagnosis
6
34
56
Behavior on CPU/Master Stop
7
57 ... 75
Reserved = 0
26
76
Input 1 action
28
77
Input 2 - (see Input 1 action)
30
78
Input 3 - (see Input 1 action)
32
79
Input 4 - (see Input 1 action)
80 ... 95
Reserved = 0
PROFINET Communication Module for SIRIUS Soft Starter 3RW44
Manual, 12/2013, A5E31996495002A/RS-AA/001
A.1 Data formats and data records
Only in
Value range/ [coding]
data
record
131
Direct on line [0]
•
Voltage ramp [1]
•
Torque control [2]
•
Motor heating [3]
•
Voltage ramp + current limiting
•
[5]
Torque control + current
•
limiting [6]
Coasting down [0]
•
Torque control [2]
•
Pump stop [3]
•
DC braking [4]
•
Combined braking [5]
•
X
X
Disable [0]
•
Enable [1]
•
X
Switch substitute value [0]
•
Hold last value [1]
•
X
No action (default) [0]
•
Manual operation local mode
•
[6]
Emergency start [7]
•
Slow speed [10]
•
Quick stop [11]
•
Trip Reset [12]
•
Motor right with PS1 [16]
•
Motor left with PS1 [17]
•
Motor right with PS2 [18]
•
Motor left with PS2 [19]
•
Motor right with PS3 [20]
•
Motor left with PS3 [21]
•
X
X
X
Appendix
Factor
99