1. When the user performs the configuration, the device is given a technological name (e.g.:
Motor-1). STEP 7 automatically assigns an IP address. This requires that "Assign IP
address via IO controller" is activated.
2. The user assigns the device name to an IO device based on the MAC address and
transfers the name, for example, with the "Edit Ethernet Node" function".
3. The user downloads the configuration to the IO controller
4. The IO controller assigns the IP parameters based on the device name during startup.
Configuring the device name using the "Soft Starter ES 2007" software and transferring it to
the device
In this case, the device name must be configured under "Device parameters > Field bus
interface > PROFINET Parameters > Station" and the "Overwrite device name in device"
parameter must be activated.
Note
Transferring the device parameters
It is always possible to transfer the device parameters via the local device interface.
If the IP address has already been configured in a different way, the device parameters can
be transferred via PROFINET, too.
Note
Changing the device name
Any change of the device name using the "PROFINET Parameters" dialog box of "Soft
Starter ES 2007" requires a restart of the communication interface. A new start interrupts all
Ethernet and PROFINET links and reestablishes them afterward.
Transferring IP parameters
The IP parameters, consisting of IP address, subnet mask, and router can also be assigned
in various ways and transferred to the IO device.
PROFINET Communication Module for SIRIUS Soft Starter 3RW44
Manual, 12/2013, A5E31996495002A/RS-AA/001
5.2 Configuring the properties of 3RW44 PN as IO device
Configuring/assigning parameters
29