Output circuit
Item
Model
Output type
Output voltage
Load current
ON residual voltage
ON leakage current
*1
Internal circuit diagram
*1 Below is a table giving the COM_OUT (output common) and output signal connection correspondence.
Terminal name
HIGH1
PASS1
LOW1
Output terminal
name
ALARM
BUSY1
ENABLE1
Important
• Connect a load that matches the output specifications. Short-circuit can cause sensor breakdown.
• Keep the load current less than or equal to the specification value. Exceeding the specification value could cause
damage to the output circuit.
50
Wiring
Specifications
ZW-CE10T
NPN
DC21.6 to 30 V
50 mA max.
1.2 V max.
0.1 mA max.
Internal
circuit
COM_OUT1
COM_OUT2
BANK_OUT1
BANK_OUT2
BANK_OUT3
ZW-CE15T
PNP
DC21.6 to 30 V
50 mA max.
1.2 V max.
0.1 mA max.
Output
terminals
L
Load
Internal
+
circuit
COM_OUT1/2
COM_OUT1/2
+
Load
L
Output
terminals