Event name
SYNC input error
Meaning
SYNC input processing was not executed correctly.
Source
EtherCAT master function module
Error attributes
Level
Effects
User program
Indicators
EtherCAT NET RUN
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
SYNC input turned ON in the FUN
mode.
Attached
None
information
Precautions/
None
Remarks
Event name
TIMING input error
Meaning
TIMING input processing was not executed correctly.
Source
EtherCAT master function module
Error attributes
Level
Effects
User program
Indicators
EtherCAT NET RUN
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
TIMINGx input turned ON in the
FUN mode.
TIMINGx input turned ON or OFF
while RESETx input was ON.
TIMINGx input turned ON in a non-
measurement state.
TIMINGx input turned ON before
the "delay time + sampling time"
elapsed.
Attached
None
information
Precautions/
None
Remarks
278
Error Messages
Minor fault
Continues
EtherCAT NET ERR
Data type
Correction
Switch to the RUN mode, and turn
SYNC input ON.
Source details
Minor fault
Recovery
Continues
Operation
EtherCAT NET ERR
Data type
Correction
Switch to the RUN mode, and turn
TIMINGx input ON.
Modify the program so that
TIMINGx input turns ON or OFF
when RESETx input is OFF.
Modify the program so that
TIMINGx input turns ON when the
sensor is ready for measurement.
Modify the program so that the
"delay time + sampling time" is
shorter than the TIMING input
interval.
Event code
7492 0000Hex
Slave
Error reset
(after
cancellation of
slave error)
SYNC input processing is not executed.
EtherCAT LINK/ACT
Name
Prevention
Event code
7493 0000Hex
Slave
Detection
timing
Error reset
Log category
(after
cancellation of
slave error)
TIMING input processing is not executed.
EtherCAT LINK/ACT
Name
Prevention
Program so that TIMINGx input
turns ON or OFF when RESETx
input is OFF.
Program so that TIMINGx input
turns ON when the sensor is ready
for measurement.
Program so that the "delay time +
sampling time" is shorter than the
TIMING input interval.
When instructed
by the user
System
When instructed
by the user
System