Honeywell ComfortPoint Open Installation And Commissioning Instructions

Honeywell ComfortPoint Open Installation And Commissioning Instructions

Mixed panel bus i/o module cpo-io830a

Advertisement

CONTENTS
Safety Information ................................................................ 2
General Safety Information ............................................... 2
Safety Information as per EN60730 .................................. 2
Comfort Point System Overview ......................................... 3
CPO-IO830A Description ..................................................... 4
Overview ........................................................................... 4
Safety Feature .................................................................. 4
Technical Data .................................................................. 5
Analog Inputs ....................................................................... 5
Analog Outputs..................................................................... 5
Binary Inputs ..................................................................... 5
Relay Outputs....................................................................... 6
Status LED Behavior......................................................... 6
Panel Bus Topologies ....................................................... 6
Updating Software and Firmware ..................................... 6
Power Supply .................................................................... 6
Fusing ............................................................................... 7
Wiring and Set-Up ............................................................ 7
General Safety Considerations ............................................. 7
Wiring Push-In Terminals ..................................................... 7
Connecting Single Bus Controller Systems ........................... 7
Cable Specifications ......................................................... 8
Shielding and Protective Earth Grounding ............................ 8
Tools and Other Connected Devices ................................ 8
General ................................................................................ 8
Terminals .......................................................................... 9
Connection Examples ..................................................... 10
Accessories .................................................................... 11
XS830 Auxiliary Terminal Package ..................................... 11
XS831 Auxiliary Terminal Package ..................................... 11
XS816 Bridge Connectors .................................................. 11
Pluggable Panel Bus I/Os ................................................... 12
Dimensions ..................................................................... 13
Troubleshooting the CPO-IO830A .................................. 14
Power LED ......................................................................... 14
Service LED ....................................................................... 14
Trademark Information
TM
BACnet
is a trademark of ASHRAE Inc.
TM
ComfortPoint
Open is a trademark of Honeywell Inc.
Copyright © 2012 Honeywell GmbH ● All Rights Reserved
ComfortPoint Open
MIXED PANEL BUS I/O MODULE CPO-IO830A
INSTALLATION AND COMMISSIONING INSTRUCTIONS
EN1B-0498GE51 R0512

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell ComfortPoint Open

  • Page 1: Table Of Contents

    Service LED ............... 14 Appendix: NTC 20 kΩ Sensor Characteristics ....15 Trademark Information BACnet is a trademark of ASHRAE Inc. ComfortPoint Open is a trademark of Honeywell Inc. Copyright © 2012 Honeywell GmbH ● All Rights Reserved EN1B-0498GE51 R0512...
  • Page 2: Safety Information

    Class 3 ► Use only accessory equipment which comes from or has Overvoltage 24 V-powered controls: Category I been approved by Honeywell. category mains-powered controls: Category II ► It is recommended that devices be kept at room tem- Rated impulse 330 Vac for Category I perature for at least 24 hours before applying power.
  • Page 3: Comfort Point System Overview

    ComfortPoint Open System Comfort Point System Overview The ComfortPoint Open System consists of the CPO-PC-6A Plant Controller, Mixed Panel Bus I/O Module CPO-IO830A, and other field-level devices as well as management-level systems connected via the controller’s various interfaces and bus connections.
  • Page 4: Cpo-Io830A Description

    A5 B5 A6 B6 A7 B7 A8 B8 Binary Inputs Analog Inputs Analog Outputs 24V Relays Honeywell ComfortPoint Open NO1 NO2 NO3 NO4 NO5 NO6 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 Install. Instr. MU1B-0463GE51 Fig.
  • Page 5: Technical Data

    ComfortPoint Open System Technical Data Analog Outputs Number: Analog Inputs 0…11 Vdc / ± 1 mA, default; also con- Characteristics: figurable as binary outputs (0 V / 10 V) Number: Accuracy: ±150 mV Characteristics: linear graph 0..10 Vdc with pull-up, 0(2)…10 Vdc without pull-up;...
  • Page 6: Relay Outputs

    Panel Bus are allowed. Max. distance between Panel Bus I/O modules and CPO-PC-6A: 40 m. No bus termination is necessary, and the Panel Bus is polarity-insensitive. See also ComfortPoint Open Plant Controller – Installation and Commissioning Instructions (EN1B-0462GE51) for more information.
  • Page 7: Fusing

    ComfortPoint Open System Fusing Wiring Push-In Terminals The CPO-IO830A is equipped only with push-in terminals. The choice of appropriate fusing is dependent upon the given Use only copper wires, with a thickness of 28-14 AWG (0.14 connection scenario (i.e., cable lengths and the use of a …...
  • Page 8: Cable Specifications

    The CPO-IO830A is controlled by the CPO-PC-6A Plant Controller. During engineering using ComfortPoint Open Studio – see also ComfortPoint Open Plant Controller – User Guide (EN2B-0363GE51) – the user must define: • the bus type of the individual RS485 interfaces (i.e., CP- IO Bus, Field Bus, Modbus, Panel Bus, or BACnet Bus) •...
  • Page 9: Terminals

    ComfortPoint Open System Terminals 24 V RELAYS EXTERNAL JUMPERS JUMPERS 24VAC FOR RELAY BINARY ANALOG ANALOG COMMON INPUTS INPUTS OUTPUTS AI5 AI6 AI7 AI8 B10 B11 B12 AO5 AO6 AO7 B8 B9 8 9 10 11 12 17 18 19 20 25 26 27 AI2 AI3 AI4 AI1 AI2...
  • Page 10: Connection Examples

    Error! Use the Home tab to apply Überschrift 1 to the text that you want to appear here. ComfortPoint Open System Connection Examples B10 B11 B12 B7 B8 B9 9 10 11 12 B1 B2 B3 B4 B5 B6 G1 G2 41 42 Fig.
  • Page 11: Accessories

    ComfortPoint Open System Accessories Terminal Assignment A1 B1 A2 B2 A3 B3 A4 B4 G1 A5 B5 A6 B6 A7 B8 G2 XS830 Auxiliary Terminal Package 7 8 9 7 8 9 Features • For mounting onto the top of already-installed CPO- IO830A modules in order to equip them with additional terminals.
  • Page 12: Pluggable Panel Bus I/Os

    Honeywell Honeywell PANEL BUS PANEL BUS PANEL BUS PANEL BUS ComfortPoint Open ComfortPoint Open NO1 NO2 NO3 NO4 NO5 NO6 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 Install. Instr.
  • Page 13: Dimensions

    54.4 Binary Inputs Analog Inputs Analog Outputs 24V Relays Honeywell ComfortPoint Open NO1 NO2 NO3 NO4 NO5 NO6 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 Install. Instr. MU1B-0463GE51 61.1 Fig.
  • Page 14: Troubleshooting The Cpo-Io830A

    Error! Use the Home tab to apply Überschrift 1 to the text that you want to appear here. ComfortPoint Open System Troubleshooting the CPO-IO830A Diagnostics and application debugging of the CPO-IO830A can be performed via the CPO-PC-6A using ComfortMan. Furthermore, the CPO-IO830A also features a power LED and service LED which can likewise be used for troubleshooting purposes.
  • Page 15: Appendix: Ntc 20 Kω Sensor Characteristics

    ComfortPoint Open System Appendix: NTC 20 kΩ Sensor Characteristics The following sensor characteristics do not include failures due to: sensor failures; wiring resistance or wiring failures; misreadings due to a meter connected to measure resistance or voltage at the input. Temp.
  • Page 16 Error! Use the Home tab to apply Überschrift 1 to the text that you want to appear here. ComfortPoint Open System Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative: Automation and Control Solutions Honeywell GmbH Böblinger Strasse 17...