Choose Gas Control Location; Install Piping To Gas Control; Install Gas Control - Honeywell VR8304 Manual

Intermittent pilot dual automatic valve combination gas controls
Hide thumbs Also See for VR8304:
Table of Contents

Advertisement

FIG. 2-INSTALL FLANGE TO GAS CONTROL.
HORIZONTAL :
I
I
I
I
I
I I
I I
I
:
I
I
I
'
RISER
I
I
I I
I I
·
...._,,
&
ALL BENDS IN METALLIC TUBING SHOULD BE SMOOTH.
fil
CAUTION, SHUT OFF THE MAIN GAS SUPPLY BEFORE REMOVING END CAP
TO PREVENT GAS FROM FILLING THE WORK AREA. TEST FOR GAS LEAK·
AGE WHEN INSTALLATION IS COMPLETE.
FIG. 3-INSTALL SEDIMENT TRAP.
that are used for installing the gas control. After the adapter
is installed, the gas control is attached to the adapter as
outlined above. Note that using an adapter increases the
overall length of the gas control.

CHOOSE GAS CONTROL LOCATION

Do not locate the gas control where it may be affected
by steam cleaning, high humidity, dripping water, corrosive
chemicals, dust or grease accumulation, or excessive
heat. To ensure proper operation, follow these guidelines.
• Locate gas control in a well ventilated area.
• Mount gas control high enough above the cabinet
bottom to avoid exposure to flooding or splashing
DRDP
I I
PIPED
Ii
GAS
I
SUPPLY
I
I
I
DROP
TUBING
GAS
SUPPLY
3 INCHES [76 mm)
M INIMUM
• Ensure the ambient temperature does not exceed
• Cover gas control if appliance is cleaned with water,
• Avoid locating gas control where exposure to cor­
Locate the gas control in the appliance vestibule on the
gas manifold. In replacement applications, locate the gas
control in the same location as the old gas control.

Install Piping to Gas Control

All piping must comply with local codes and ordinances
or with the National Fuel Gas Code (ANSI Z223.1 NFPA
No. 54), whichever applies. Tubing installation must comply
with approved standards and practices.
1. Use new, properly reamed pipe free from chips. If
tubing is used, ensure the ends are square, deburred and
clean. All tubing bends must be smooth and without
deformation.
2. Run pipe or tubing to the gas control. If tubing is used,
obtain a tube-to-pipe coupling to connect the tubing to the
gas control.
3. Install sediment trap in the supply line to the gas
RISER
control. See Fig. 3.
PIPED
GAS

Install Gas Control

SUPPLY
1.
from the upright position of the gas control knob, including
vertically.
2. Mount the gas control so gas flow is in the direction
of the arrow on the bottom of the gas control.
3. Thread pipe the amount shown in Table 4 for inser­
tion into the gas control or adapter. DO NOT THREAD
PIPE TOO FAR. Valve distortion or malfunction may result
if the pipe is inserted too deeply into the gas control.
TABLE 4-NPT PIPE THREAD LENGTH IN INCHES.
PIPE
SIZE
3/8
6933E
4. Apply a moderate amount of good quality pipe com­
pound (DO NOT use Teflon tape) to pipe only, leaving two
end threads bare. On LP installations, use compound
resistant to LP gas.
TW O IM PE RFECT �t �T RO L
THREADS
THREAD PIPE THE AMOUNT
SHOWN IN TABLE FOR
INSERTION INTO
GAS CONTROL.
FIG. 4-USE MODERATE AMOUNT OF PIPE COM­
5
water.
the ambient temperature ratings for each compo­
nent.
steam, or chemicals or to avoid dust and grease
accumulation.
rosive chemical fumes or dripping water are likely.
Mount the gas control
0-90
THREAD PIPE
THIS AMOUNT
9/16
1/2
3/4
3/4
13/16
APPLY A MODERATE AMOUNT
OF PIPE COMPOUND TO PIPE
ONLY (LEAVE TWO END
THREADS BARE).
POUND.
degrees, in any direction,
MAXIMUM DEPTH
PIPE CAN BE
INSERTED INTO
CONTROL
3/8
1/2
3/4
313F
68-0108-1