Connection; Manually Unlocking Power-Unit Doors; Connecting Ground; Table 6-2 Cable Cross-Sections - Siemens 6SL3845-2NN41-8AD2 Operating Instructions Manual

Medium-voltage drive
Table of Contents

Advertisement

Table 6-2
Object
Power cable
Cabinet protective conductor
See also
Torques (Page 143)
6.5

Connection

6.5.1

Manually unlocking power-unit doors

To ensure operator protection, the drive is equipped with an electromechanical door
interlocking system. The doors cannot be opened until the make-proof grounding switch has
been closed. In the event of a complete voltage failure including failure of the auxiliary voltage,
the doors cannot be released via the grounding switch.
Because the drive is not yet connected, the doors are locked electromechanically. In order to
facilitate assembly and installation of the drive, the doors can be opened manually.
See also
Opening the doors (Page 134)
6.5.2

Connecting ground

Danger to life as a result of insufficient grounding
The drive must be grounded to ensure that it operates safely and reliably. If the drive is
operated with insufficient grounding, then the protection and monitoring functions can fail.
Death, serious injury, or material damage will result.
● To ensure the correct functioning of the protection and monitoring equipment, ground the
Each cabinet has a grounding lug for grounding the components installed in the cabinet. It is
located at the bottom of the cabinet. Connect the cabinets securely to the plant grounding
system via these grounding lugs.
SINAMICS SM150 6SL3845-2NN41-8AD2
Operating Instructions Rev.201910281310 EXAMPLE
Cable cross-sections
DANGER
device.
Cross-section
Max. 240 mm
2
Max. 120 mm²
Electrical connection
Comments
Max. six parallel power cables
-
6.5 Connection
87