SETUP Menu

Emergency Override Definitions (with LCI or BCI module installed)

When an LCI or BCI module is installed, the user can initiate one of five (5) Emergency Override sequences that have the
following predefined unit operation via LonTalk or BACnet Communication:
PRESSURIZE
Supply Fan – On
Inlet Vanes - Open (if equipped)
Return Fan VFD – Min
Return Fan / Exhaust Damper - Off / Closed (if equipped)
OA Dampers – Open
Heat - All heat stages Off (staged gas and elec.); Hydronic heat & Mod Gas Heat output at 0%.
Occupied / Unoccupied output – Energized
VO Relay - Energized (with VOM module installed)
VCM Preheater State - Off (with VCM installed)
DEPRESSURIZE
Supply Fan – Off
Inlet Vanes - Closed (if equipped)
Return Fan VFD – Max
Return Fan / Exhaust Damper - On / Open (if equipped)
OA Dampers – Closed
Heat - All heat stages Off (staged gas and elec.); Hydronic heat & Mod Gas Heat output at 0%.
Occupied / Unoccupied output - De-energized
VO Relay - Energized (with VOM module installed)
VCM Preheater State - Off (with VCM installed)
PURGE
Supply Fan – On
Inlet Vanes - Open (if equipped)
Return Fan / Exhaust Damper - On / Open (if equipped)
Return Fan VFD – Max
OA Dampers – Open
Heat - All heat stages Off (staged gas and elec.); Hydronic heat & Mod Gas Heat output at 0%.
Occupied / Unoccupied output – Energized
VO Relay - Energized (with VOM module installed)
VCM Preheater State - Off (with VCM installed)
SHUTDOWN
Supply Fan – Off
Inlet Vanes - Closed (if equipped)
Return Fan / Exhaust Damper - Off / Closed (if equipped)
Return Fan VFD – Min
OA Dampers – Closed