Trane S*HF*20-75 Troubleshooting Manual page 110

Commercial single zone rooftop air conditioner or commercial rooftop air handlers, with variable air volume (vvda/vvzt) controls or constant air volume (cvda/cvzt) controls intellipak i series; intellipak ii series;
Table of Contents

Advertisement

SERVICE MODE Menu (Local Human Interface only)
End Of Submenu (NEXT) For Service Mode
• Press Next/Previous keys to navigate.
Relay State =
Hydro Heat/Chilled Water Output
Table 8: Hydronic Heat/Chilled Water Relay
State/Relays
OFF
Cool On
Heat On
Override
Notes:
1. K1 turns ON when the output is commanded > 0%.
2. Override occurs with Freezestat or service test request.
• Press Next/Previous keys to navigate.
Relay State =
Mod Gas Heat/Chilled Water Output
Table 9: Modulating Gas Heat / Chilled Water Relay
State/Relays
OFF
Cool On
Heat On
Override
Note: K1 turns ON when the output is commanded > 0%.
• Press Next/Previous keys to navigate.
Chilled Water
Actuator
• Press Next/Previous keys to navigate.
Hydronic Heat
Actuator
• Press Next/Previous keys to navigate.
110
K11
K12
OFF
OFF
ON
ON
OFF
OFF
ON
OFF
K11
K12
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
Used With: All Units w/DX Cooling
Used With: Air Handlers w/Chilled
HEAT ON
Water Cooling and Hydronic Heat
0%
Possible Values:
Relay State:
HEAT ON, COOL ON, OVERRIDE
Output: 0 to 100%
K1
OFF
Note: The relays on the HEAT module,
OFF
and associated wiring, are used to route
Note 1
the 0 to 10VDC modulating output to the
Chill Water and Hydronic Heat actuators.
Note 2
[See "
Table 8: Hydronic Heat/Chilled
Water Relay
Used With: Air Handlers w/Chilled
HEAT ON
Water Cooling and Modulating Gas Heat
0%
Possible Values:
Relay State: HEAT ON, COOL ON
Output: 0 to 100%
K1
Note: The relays on the HEAT module,
OFF
and associated wiring, are used to route
OFF
the 0 to 10VDC modulating output to the
Note 1
Chill Water and Mod Gas Heat actuators.
OFF
[see "
Table 9: Modulating Gas Heat /
Chilled Water Relay
Used With: Air Handlers w/Chilled
Water Cooling (If Heating Unit, Hydronic
0%
or Modulating Gas Is Not Installed)
Possible Values: 0 to 100%
Used With: Hydronic Heat Units, (If Air
Handler Unit, Chill Water Is Not Installed)
0%
Possible Values: 0 to 100%
on Left"]
on Left"]
RT-SVP07B-EN