Trane S*HF*20-75 Troubleshooting Manual page 40

Commercial single zone rooftop air conditioner or commercial rooftop air handlers, with variable air volume (vvda/vvzt) controls or constant air volume (cvda/cvzt) controls intellipak i series; intellipak ii series;
Table of Contents

Advertisement

STATUS Menu
CONTROLLING SETPOINT STATUS SUBMENU SCREENS
Controlling SETPOINT Status Submenu
Press ENTER to View Data in This Submenu
• Press the Next key to skip this Submenu.
Active Supply Air Cooling STP From
HI (KEYPAD) SETPOINT MENU
• Press Next/Previous keys to navigate.
Active Supply Air Heating STP From
HI (KEYPAD) SETPOINT MENU
• Press Next/Previous keys to navigate.
Active Daytime Warmup Setpoints
Initiate:
67 °F
• Press Next/Previous keys to navigate.
Active Occupied Zone Cooling STP From
HI (KEYPAD) SETPOINT MENU
• Press Next/Previous keys to navigate.
40
Is
Is
Terminate:
is
Used With: All Units
Used With: VVDA or CVDA Units
Possible Values:
55°F
HI (KEYPAD) SETPOINT MENU
ZONE SENSOR SETPOINT INPUT
NSB PANEL SETPOINT INPUT
GBAS 0-5 VDC MODULE
GBAS 0-10 VDC MODULE
BAS/NETWORK
Range: 40 to 90ºF
Used With: VVDA or CVDA Units w/
Hydronic Heat, Modulating Gas Heat, or
100°F
IpakII w/Electric Heat
Possible Values:
HI (KEYPAD) SETPOINT MENU
ZONE SENSOR SETPOINT INPUT
GBAS 0-5 VDC MODULE
GBAS 0-10 VDC MODULE
BAS/NETWORK
Range: 40 to 180ºF
Used With: Units w/DWU ENABLED
Possible Values:
71 °F
Initiate: 50 to 87ºF
Terminate: 53 to 90ºF
Used With: CVZT Units w/DX Cooling
Possible Values:
71°F
HI (KEYPAD) SETPOINT MENU
ZONE SENSOR SETPOINT INPUT
NSB PANEL SETPOINT INPUT
GBAS 0-5 VDC MODULE
GBAS 0-10 VDC MODULE
BAS/NETWORK
Range: 52 to 90ºF
RT-SVP07B-EN