Trane S*HF*20-75 Troubleshooting Manual page 22

Commercial single zone rooftop air conditioner or commercial rooftop air handlers, with variable air volume (vvda/vvzt) controls or constant air volume (cvda/cvzt) controls intellipak i series; intellipak ii series;
Table of Contents

Advertisement

General Status Display
Table 2. Factory Presets List (continued)(Note: Listed Items availability is dependent on unit configuration.
Adjustable Function
Bias
Zone Control Modulating Heat Gains
Proportional
Reset Time
Rate Time
Bias
SZVAV Heating Control Gains
Proportional
Reset Time
Rate Time
Bias
Rapid DX Interstage Timing
Default Setpoints
(VAV/SZVAV) 1
Supply Air Cooling
(VAV/SZVAV) 1
Supply Air Heating
SA Cool Deadband
SA Heat Deadband
DWU Initiate
DWU Terminate
Occupied Zone Cooling
Occupied Zone Heating
Zone Derived Setpoint
Unoccupied Zone Cooling
Unoccupied Zone Heating
Unoccupied Zone MWU
1
Rapid Restart Critical Temp
Occ Dehumidification
Occ Dehumid Hysteresis Offset
Unocc Dehumidification
Unocc Dehumid Hysteresis Offset
Supply Air Reheat Setpoint
Supply Air Reheat Deadband
Maximum Reheat Valve Limit
Dehumid Ovrd High Zone Temp
Dehumid Ovrd Low Zone Temp
Cond Coil Purge Interval
Occ Humidification
Occ Humidification Hysteresis Offset
Unocc Humidification
Unocc Humidification Hysteresis Offset
Economizer Cooling Setpoint Suppression (CV)
Reference Enthalpy
Economizer Drybulb Enable Stpt
22
Factory Preset
Changed To
0 deg F
___________
10.0 % F
___________
DISABLE
___________
0 Sec
___________
0 deg F
___________
8.0 % F
___________
1200 Sec
___________
0 Sec
___________
0 deg F
___________
30 Sec
___________
55 F / 50 F
___________
100 F / 105 F
___________
8.0 F
___________
4.0 F
___________
67 F
___________
71 F
___________
74 F
___________
71 F
___________
4 F
___________
85 F
___________
60 F
___________
72 F
___________
90 F
___________
60 %
___________
5 %
___________
60 %
___________
5 %
___________
70 F
___________
4 F
___________
85 %
___________
75 F
___________
68 F
___________
90 Min
___________
30 %
___________
5 %
___________
30 %
___________
5 %
___________
3 F
___________
25 BTU/LB
___________
75 F
___________
To adjust
press...
Setup
Setup
Setup
Setup
Setup
Setup
Setup
Setup
Setup
Setup
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
RT-SVP07B-EN