General Status Display
Table 2. Factory Presets List (continued)(Note: Listed Items availability is dependent on unit configuration.
Adjustable Function
Reset Cool Start Temp (Zone/OA)
Reset Cool End Temp (Zone/OA)
Reset Cool Max Amount
SA Temp Reset Heat
Reset Heat Start Temp (Zone/OA)
Reset Heat End Temp (Zone/OA)
Reset Heat Max Amount
VAV Box Stroke Time
Max Occ. IGV/VFD Command
Economizer Control
Economizer Control Enable Type
Unoccupied Economizer
Head Pressure Control
Sump Drain Relay Control (on power loss)
Sump Purge Interval Time
Sump Purge Duration Time (IPak-I/IPak-II)
Sump Water Heater Setpoint
Low Limit (Air-cooled/Water-cooled)
Upper Limit
Temporary low limit suppression
Efficiency check point
Low amb. control point (Air-cooled/Water-cooled)
1
Alternate Refrigerant Type
Sensor Source Selection
Daytime Warm-Up
Occupied Zone Control
Unoccupied Zone Control
Morning Warm-Up
Space Humidity Control
Dehumid OVRD Zone Temp
Zone Reset Function
Rapid Restart Function
Monitor
Outside Air Ventilation
Demand Control Ventilation
Active/Passive DCV Control
OA Flow Compensation
OA Flow C02 Reset (IPak-INon-DCV)
CO2 Start (IPak-I Non-DCV)
CO2 Max (IPak-I Non-DCV)
18
Factory Preset
(72/90)
(69/70)
(65/10)
(68/60)
6 Min
100 %
Drybulb
Enable
Drain
Disabled
1
120/60 sec.
1
80/70 deg F
120 deg F
20 deg F
105 deg F
90/80 deg F
1
Disabled
RTM Zone Temp
RTM Zone Temp
RTM Zone Temp
RTM Zone Temp
RTM Space Humidity
RTM Zone Temp
RTM Zone Temp
ECEM Return Temp
RTM Zone Temp
Disable
Passive
Enabled
Disabled
Changed To
___________
___________
5
___________
None
___________
___________
___________
10
___________
___________
___________
___________
___________
___________
___________
___________
38 F
___________
___________
___________
___________
___________
___________
___________
___________
___________
___________
___________
___________
___________
___________
___________
___________
___________
___________
___________
___________
800
___________
1000
___________
To adjust
press...
Setup
Setup
Setup
Setup
Setup
Setup
Setup
Setup
Setup
Setup
Setup
Setup
Setup
Setup
Setup
Setup
Setup
Setup
Setup
Setup
Setup
Setup
Setup
Setup
Setup
Setup
Setup
Setup
Setup
Setup
Setup
Setup
Setup
Setup
Setup
Setup
RT-SVP07B-EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents