STATUS Menu
Condenser Sump Drain Relay:
Condenser Sump Drain Valve:
"Relay" and "Valve" states are configurable based on the need to
hold water in the sump or drain it on power loss. See the IOM, and
"
Table 7: Sump Drain Valve States"
section for further information.
• Press Next/Previous keys to navigate.
Cond Sump Water Level Max Input:
Cond Sump Water Level Min Input:
• Press Next/Previous keys to navigate.
External Sump Drain Request:
• Press Next/Previous keys to navigate.
Reheat Coil Pumpout Relay:
Reheat Coil Pumpout Valve:
• Press Next/Previous keys to navigate.
Dehumid Reheat
Dehumid Cooling Valve Position:
• Press Next/Previous keys to navigate.
Active Outside Air Temperature
Low Ambient Comp Lockout Temp:
• Press Next/Previous keys to navigate.
34
on page 108 in Service Test
Valve Position:
Used With: DX Cooling w/Water-Cooled
ON
Condensers
CLOSED
Possible Values:
Sump Drain Relay: ON, OFF
Sump Drain Valve: CLOSED, OPEN
Used With: DX Cooling w/Water-Cooled
OPEN
Condensers
CLOSED
Possible Values:
Max Input: CLOSED, OPEN
Min Input: CLOSED, OPEN
Used With: DX Cooling w/Water-Cooled
INACTIVE
Condensers
Possible Values: ACTIVE, INACTIVE
Used With: DX Cooling w/
OFF
Dehumidification
CLOSED
Possible Values:
Relay: ON, OFF
Valve: CLOSED, OPEN
Used With: DX Cooling w/
0%
Dehumidification
100%
Possible Values:
Reheat Valve: 0 to Max Reheat Valve
Position Setpoint (see Setpoints
Menu)
Cooling Valve: 10 to 100%
Used With: DX Cooling
70.0°F
Possible Values:
50°F
Active Outside Air Temp: -40 to
200.0ºF Lockout Temp: -20 to 80ºF
Default(s):
Standard: 50ºF
Low-Amb. w/Hot Gas Bypass: 0ºF
Low-Amb. w/o Hot Gas Bypass: 10ºF