Trane S*HF*20-75 Troubleshooting Manual page 68

Commercial single zone rooftop air conditioner or commercial rooftop air handlers, with variable air volume (vvda/vvzt) controls or constant air volume (cvda/cvzt) controls intellipak i series; intellipak ii series;
Table of Contents

Advertisement

SETUP Menu
Ventilation Override Mode C - (Exhaust)
Supply Fan – Off
Inlet Vanes - Closed (if equipped)
Return Fan / Exhaust Damper – On / Open (if equipped)
Return Fan VFD – Max
OA Dampers – Closed
Heat - All heat stages Off (staged gas and elec.); Hydronic heat & Mod Gas Heat output at 0%.
Occupied / Unoccupied output – Deenergized
VO Relay – Energized
VCM Preheater State - Off (with VCM installed)
Ventilation Override Mode D - (Purge)
Supply Fan – On
Inlet Vanes / VFD - Open / 100%
Return Fan VFD – Max
Return Fan / Exhaust Damper - On / Open (if equipped)
OA Dampers – Open
Heat - All heat stages Off (staged gas and elec.); Hydronic heat & Mod Gas Heat output at 0%.
Occupied / Unoccupied output – Energized
VO Relay – Energized
VCM Preheater State - Off (with VCM installed)
Ventilation Override Mode E - (Purge with Duct Pressure Control)
Supply Fan – On
Return Fan VFD – Max
Inlet Vanes / VFD - Open/100% (Ctrl'd by SA Press control function, SA Press High Limit is disabled)
Return Fan / Exhaust Damper - On / Open (if equipped)
OA Dampers – Open
Heat - All heat stages Off (staged gas and elec.) Hydronic & Mod Gas Heat output at 0%.
Occupied / Unoccupied output – Energized
VO Relay – Energized
VCM Preheater State - Off (with VCM installed)
Note:
1. The five VOM modes A, B, C, D, E will have the factory defaults set to the above defined values.
2. "OFF" - will appear in the Ventilation Override screen after all VOM binary inputs have been reset (opened).