Trane S*HF*20-75 Troubleshooting Manual page 65

Commercial single zone rooftop air conditioner or commercial rooftop air handlers, with variable air volume (vvda/vvzt) controls or constant air volume (cvda/cvzt) controls intellipak i series; intellipak ii series;
Table of Contents

Advertisement

Maximum OA Flow at Design Conditions
OA Normalization:
• Press Next/Previous keys to navigate.
OA Flow Calibration Data
Altitude:
This correction factor is used to adjust airflow calculations due to
density of air at different altitudes.
Table 5. Flow Calibration - Altitude Correction Factor C.F.
Feet
Meters
0
0
500
150
1000
300
1500
450
2000
600
2500
750
3000
900
3500
1050
4000
1200
4500
1350
5000
1500
• Press Next/Previous keys to navigate.
End of Submenu (NEXT) to Enter SETUP
• Press Next/Previous keys to navigate.
RT-SVP07B-EN
C.F.
Feet
Meters
1.00
5500
1650
0.99
6000
1800
0.98
6500
2000
0.97
7000
2150
0.97
7500
2300
0.96
8000
2450
0.95
8500
2600
0.94
9000
2750
0.93
9500
2900
0.92
10000
3050
0.91
Used With: Units w/Return Fan and
Fresh Air Measurement (VCM) w/DCV,
350 CCFM
Units w/Energy Recovery Wheel Option
Factory Preset: 1 CCFM
Possible Values: 0 to Max Unit Airflow
[See "Max Unit Airflows" in Setpoints
Section Below]
Used With: Units w/Return Fan and
Fresh Air Measurement (VCM)
 0 Ft.
Factory Preset: 0 Ft (0 m)
Possible Values:
[See
Correction Factor
below.]
C.F.
0.91
0.90
0.89
0.88
0.87
0.86
0.85
0.85
0.84
0.83
SETUP Menu
"Table 5. Flow Calibration - Altitude
C.F." for assignments
65