DEVICE CHARACTERISTICS SETUP DEFINITIONS SCREENS
Device Characteristic Setup Definitions
Press ENTER to review or Adjust
• Press Next/Previous keys to navigate.
Actuator Setup
Max Stroke Time
• Press Next/Previous keys to navigate.
Actuator Setup
Min Voltage
• Press Next/Previous keys to navigate.
Actuator Setup
Max Voltage
• Press Next/Previous keys to navigate.
Actuator Setup
Direct/Reverse Act
• Press Next/Previous keys to navigate.
Actuator Setup
Max Stroke Time
• Press Next/Previous keys to navigate.
Actuator Setup
Min Voltage
Note: If the unit is configured for a Supply Fan VFD, initial setting
should be 0.0 VDC. If the unit is configured with IGV set this value
to 2.0 VDC.
• Press Next/Previous keys to navigate.
RT-SVP07B-EN
OA Damper
OA Damper
OA Damper
10.0 VDC
OA Damper
DIRECT ACTING
Supply Fan IGV/VFD
Supply Fan IGV/VFD Cmd
Used With: All Units
Used With: Units w/OA Damper
Factory Presets: 30 Sec
30 Sec
Possible Values: 1 to 255 Sec
Used With: Units w/OA Damper
Factory Presets: 2.0 VDC
2.0 VDC
Possible Values: 0 to 10.0 VDC
Used With: Units w/OA Damper
Factory Presets: 10.0 VDC
Possible Values: 0 to 10.0 VDC
Used With: Units w/OA Damper
Factory Presets: DIRECT ACTING
Possible Values: DIRECT ACTING,
REVERSE ACTING
Used With: VVDC Units
Factory Preset: 30 Sec
30 Sec
Possible Values: 1 to 255 Sec
Used With: VVDC Units
Factory Presets: 0 VDC
0.0 VDC
Possible Values: 0 to 10.0 VDC
SETUP Menu
77