Trane S*HF*20-75 Troubleshooting Manual page 61

Commercial single zone rooftop air conditioner or commercial rooftop air handlers, with variable air volume (vvda/vvzt) controls or constant air volume (cvda/cvzt) controls intellipak i series; intellipak ii series;
Table of Contents

Advertisement

Sump Water Heater Setpoint:
Low Sump Temp Activates Heater Output
• Press Next/Previous keys to navigate.
Cond Temp Control Band
Lower Limit:
• Press Next/Previous keys to navigate.
Cond Temp Control Band
Temporary Low Limit Suppression:
• Press Next/Previous keys to navigate.
Cond Temp
Efficiency Check Point:
• Press Next/Previous keys to navigate.
Cond Temp
Low Ambient Control Point:
Low Ambient Dampers control condensing temperature to this
value.
• Press Next/Previous keys to navigate.
Alternate Unit Refrigerant Type: ENABLED
Units w/R22 should have this set to ENABLED
• Press Next/Previous keys to navigate.
End of Submenu (NEXT) to Enter SETUP
• Press Next/Previous keys to navigate.
RT-SVP07B-EN
80°F Upper Limit: 120°F
Used With: Units w/Water-Cooled
38°F
Condensers and Sump Heat Installed
Factory Preset: 38ºF
Possible Values: 38 to 43ºF
Used With: Units w/DX Cooling
Factory Presets:
Upper Limit: 120ºF
Lower Limit: 80ºF
Possible Values:
Upper Limit: 110 to 130ºF
Lower Limit: 70 to 90ºF
Used With: Units w/DX Cooling
Factory Presets: 10ºF
10°F
Possible Values: 0 to 20ºF
Used With: Units w/DX Cooling
Factory Presets: 105ºF
105°F
Possible Values: 95 to 115ºF
Used With: Units w/DX Cooling w/Low
Ambient Option
90°F
Factory Presets: 90ºF
Possible Values: 80 to 100ºF
Used With: Units w/DX Cooling
Factory Presets: DISABLED
Possible Values: ENABLED/DISABLED
SETUP Menu
61

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents