Trane S*HF*20-75 Troubleshooting Manual page 36

Commercial single zone rooftop air conditioner or commercial rooftop air handlers, with variable air volume (vvda/vvzt) controls or constant air volume (cvda/cvzt) controls intellipak i series; intellipak ii series;
Table of Contents

Advertisement

STATUS Menu
OUTSIDE AIR VENTILATION STATUS SUBMENU SCREENS
Outside Air Ventilation Status Submenu
Press ENTER to View Data in this Submenu
• Press the Next key to skip this Submenu.
Demand Control Ventilation is
Space CO
Level:
2
"Space CO2 Level" is shown only if "Demand Control Ventilation"
is ENABLED
• Press Next/Previous keys to navigate.
Note: One of the three following screens will be shown based on
fresh air measurement and DCV options.
DCV Min OA Flow Target:
Deadband: 5.0 CCFM
Active Min OA Flow Setpoint:
Deadband: 6.8 CCFM
Active Min OA Flow Setpoint:
CO2 Level 1100 PPM
• Press Next/Previous keys to navigate.
Outside Air Flow
Left: 167.2 CCFM
• Press Next/Previous keys to navigate.
36
ENABLED
600 PPM
250.0 CCFM
OA Flow 234.3 CCFM
OR
140.3 CCFM
OA Flow 143.5 CCFM
OR
140.3 CCFM
OA Damper Pos:
Total: 335.4 CCFM
Right: 168.2 CCFM
Used With: Units w/Fresh Air Options
Used With: All Units
Possible Values:
DCV: ENABLED, DISABLED
CO
Level: 50 to 2200 PPM
2
Used With: Fresh Air Measurement
(VCM) w/DCV and Demand Control
Ventilation ENABLED
Possible Values:
Target: 0 to 650 CCFM
Deadband: 5.0 to 200 CCFM
OA Flow: 0 to 650 CCFM
Used With: Fresh Air Measurement
(VCM) w/DCV and Demand Control
Ventilation DISABLED
Possible Values:
Setpoint: 0 to 650 CCFM
Deadband: 5.0 to 200 CCFM
OA Flow: 0 to 650 CCFM
Used With: Fresh Air Measurement
(VCM) w/o DCV and CO2 Reset ENABLED
99 %
Possible Values:
Setpoint: 0 to 650 CCFM
CO2 Level: 50 to 2000 PPM
OA Damper Pos: 0 to 650 CCFM
Used With: Fresh Air Measurement
(VCM) w/DCV
Possible Values: 0 to 650 CCFM