STATUS Menu
Active Rapid Restart Sensor Input From
ECEM RETURN AIR TEMP INPUT
• Press Next/Previous keys to navigate.
Active Space CO
VCM SPACE CO
2
• Press Next/Previous keys to navigate.
Active Dehumid OVRD Temp Input From
RTM ZONE TEMP INPUT
• Press Next/Previous keys to navigate.
Active Zone Reset Temp Sensor Input From
RTM ZONE TEMP INPUT
• Press Next/Previous keys to navigate.
Active OA Temperature Sensor Input From
RTM OUTSIDE AIR TEMP INPUT
• Press Next/Previous keys to navigate.
Active Outside Air Humidity Input From
OA HUMIDITY SENSOR INPUT
• Press Next/Previous keys to navigate.
46
Sensor Input From
2
INPUT
is
Used With: Units w/Rapid Restart.
Possible Values:
is
82.0°F
[See "Possible Values:" Above]
Used With: Units w/Fresh Air
Measurement (VCM) w/DCV, or CO
is
600 PPM
Reset ENABLED
Possible Values:
Range: 50 to 2000 PPM
Used With: Units w/Dehumid. Option
Possible Values:
is
73.5°F
Range: -40 to 200ºF
Used With: All Units with Reset Select
not selected as None.
82.0°F
Possible Values:
[See "Possible Values:" Above]
Used With: All Units
Possible Values:
is
86.0°F
Range: -40 to 200ºF
Used With: Units w/Economizer Option
Possible Values:
is
30 %
Range: 10 to 90%
VCM SPACE CO
INPUT
2
BAS/NETWORK
RTM ZONE TEMP INPUT
NSB PANEL TEMP SENSOR INPUT
RTM AUX TEMP INPUT
HEAT MODULE AUX TEMP INPUT
ECEM RETURN AIR TEMP INPUT
BAS/NETWORK SENSOR
RTM OUTSIDE AIR TEMP INPUT BAS/
NETWORK
OA HUMIDITY SENSOR INPUT
BAS/NETWORK SENSOR
2
RT-SVP07B-EN