Actuator Setup
Max Voltage
• Press Next/Previous keys to navigate.
Actuator Setup
Direct/Reverse Act
• Press Next/Previous keys to navigate.
Actuator Setup
Max Stroke Time
• Press Next/Previous keys to navigate.
Actuator Setup
Min Voltage
• Press Next/Previous keys to navigate.
Actuator Setup
Max Voltage
• Press Next/Previous keys to navigate.
Actuator Setup
Direct/Reverse Act
• Press Next/Previous keys to navigate.
End of Submenu (NEXT) to Enter SETUP
• Press Next/Previous keys to navigate.
CONTROL ALGORITHM TUNING PARAMETERS SCREENS (Partial)
Control Algorithm Tuning Parameters
Press ENTER to Review or Adjust
Note: Contact the Trane Company before making any adjustment
to these settings.
• Press Next/Previous keys to navigate.
RT-SVP07B-EN
Exh Bypass Damper
10.0 VDC
Exh Bypass Damper
DIRECT ACTING
OA Bypass Damper
60 Sec
OA Bypass Damper
2.0 VDC
OA Bypass Damper
10.0 VDC
OA Bypass Damper
DIRECT ACTING
Used With: All IntelliPak II units with
Energy Recovery installed.
Factory Preset: 10.0 VDC
Possible Values: 0 to 10.0 VDC
Used With: All IntelliPak II units with
Energy Recovery installed.
Factory Preset: DIRECT
Possible Values: DIRECT, REVERSE
Used With: All IntelliPak II units with
Energy Recovery installed.
Factory Preset: 60 Sec
Possible Values: 1 to 255 Sec
Used With: All IntelliPak II units with
Energy Recovery installed.
Factory Preset: 2.0 VDC
Possible Values: 0 to 10.0 VDC
Used With: All IntelliPak II units with
Energy Recovery installed.
Factory Preset: 10.0 VDC
Possible Values: 0 to 10.0 VDC
Used With: All IntelliPak II units with
Energy Recovery installed.
Factory Preset: DIRECT
Possible Values: DIRECT, REVERSE
SETUP Menu
83