STATUS Menu
Circuit 1
Enter Evap: 48.5°F
"Evap Diff:" and associated value not displayed if:
1. circuit is inactive, or
2. for first ten minutes of circuit operation, or
3. HGBP is installed
"Enter Evap:" and associated value not displayed if:
1. HGBP is installed
• Press Next/Previous keys to navigate.
Circuit 1
Saturated Condensing Temp:
• Press Next/Previous keys to navigate.
Circuit 2
Enter Evap: 40.0°F
"Evap Diff:" and associated value not displayed if:
1. circuit is inactive, or
2. for first ten minutes of circuit operation, or
3. HGBP is installed
"Enter Evap:" and associated value not displayed if:
1. HGBP is installed
• Press Next/Previous keys to navigate.
Circuit 2
Saturated Condensing Temp:
• Press the Next key to navigate forward.
Circuit 1
K1: ON
K2: ON
"K2:" status not displayed, and maximum stage is 1, on water-
cooled condenser units.
• Press Next/Previous keys to navigate.
32
Evap Diff:
5.0°F
Leave Evap: 53.5°F
100.0°F
Evap Diff: 12.0°F
Leave Evap: 52.0°F
97.0°F
Cond Fan Staging
Stage 4
Used With: DX Cooling
Possible Values:
Evap Diff:
0.0 to 200.0ºF
Enter Evap: -40.0 to 200.0ºF
Leave Evap:
-40 to 200.0ºF
Used With: DX Cooling.
Possible Values:
Temp: -40.0 to 200.0ºF
Used With: DX Cooling > 40Ton
Possible Values:
Evap Diff:
0.0 to 200.0ºF
Enter Evap: -40.0 to 200.0ºF
Leave Evap:
-40 to 200.0ºF
Used With: DX Cooling > 40Ton
Possible Values:
Temp: -40.0 to 200.0ºF
Used With: DX Cooling
Possible Values:
K1: ON, OFF; K2: ON, OFF
Bottom Right Field:
OFF
Stage 1
Stage 2
Stage 3
Stage 4
RT-SVP07B-EN