GBAS 0-5VDC MODULE I/O ASSIGNMENTS SCREENS
GBAS (5VDC) Module I/O Assignments
Press ENTER to Review or Adjust
Press the Next key to skip this Submenu.
GBAS (5VDC) Analog Input 1 Assignment
NOT ASSIGNED
Note: There are 3 additional screens associated with Input
Assignments; "Analog Input 2", "Analog Input 3", and "Analog Input
4". Press the Next key to proceed through the remaining
assignments.
• Press Next/Previous keys to navigate.
GBAS (5VDC) Output 1 Alarm Assignments
Press ENTER to Review or Adjust
Press the Next key to skip this Submenu.
Note: There are 4 additional screens associated with Alarm Output
Assignments: "Alarm Output 2", "Alarm Output 3", "Alarm Output 4",
and "Alarm Output 5". The process of assigning diagnostics to those
outputs is identical to what is described here for "Alarm Output 1".
If Enter was pressed, proceed to the following 3 screens.
RT-SVP07B-EN
Used With: Units w/GBAS(5VDC) Installed
Used With: Units w/GBAS(5VDC)
Installed.
Factory Presets: NOT ASSIGNED
Possible Values:
NOT ASSIGNED
OCC ZONE COOLING SETPOINT
UNOCC ZONE COOLING SETPOINT
OCC ZONE HEATING SETPOINT
UNOCC ZONE HEATING SETPOINT
SPACE STATIC PRESSURE SETPOINT
SA STATIC PRESSURE SETPOINT
MIN OA FLOW SETPOINT
MORNING WARMUP SETPOINT
ECON DRY BULB ENABLE SETPOINT
MINIMUM POSITION SETPOINT
OCC DEHUMID SETPOINT
UNOCC DEHUMID SETPOINT
SUPPLY AIR REHEAT SETPOINT
OCC HUMIDIFICATION SETPOINT
UNOCC HUMIDIFICATION SETPOINT
Used With: Units w/GBAS(5VDC) Installed
Factory Presets:
Output 1 = Dirty Filters
Output 2 = Compressor Trip
Compressor Trip - Ckt 1
Compressor Trip - Ckt 2
Low Pressure Control Open
Low Pressure Control Open - Ckt 1
Low Pressure Control Open - Ckt 2
Comp Contactor Fail
Comp Contactor Fail - Ckt 1
Comp Contactor Fail - Ckt 2
Output 3 = Heat Fail
Output 4 = Supply Fan Failure
Output 5 = Any Active Diagnostic
Possible Values: Refer to the list of
diagnostics that can be assigned to each of
the five (5) output definitions in the
"DIAGNOSTICS Menu" section.