Evap Temperature Limit. Shut Off Circuit
if (Leaving - Entering) Exceeds:
Note: On units with Dehumidification installed a non-adjustable
Evap Temperature Limit of 40ºF is used for the Reheat Circuit only.
• Press Next/Previous keys to navigate.
Coil Frost Cutout Temperature. Shut off
Compressors If Evap Temp Is Below:
• Press Next/Previous keys to navigate.
Isolation Damper Interlock:
SA Proving Must Open Before Fan Start
If ENABLED, "SA Proving Must Open Before Fan Start" is shown. If
DISABLED, the bottom line is blank.
• Press Next/Previous keys to navigate.
End of Submenu (NEXT) to Enter SETUP
• Press Next/Previous keys to navigate.
VAV CONTROL FUNCTIONS SUBMENU SCREENS
VAV Control Functions Submenu
Press ENTER to Review or Adjust
Press the Next key to skip this Submenu.
Supply Air Temp Reset type:
Cooling:
NONE
"Heating" only shown if unit has heat installed.
• Press Next/Previous keys to navigate.
RT-SVP07B-EN
35ºF
30ºF
ENABLED
Heating:
NONE
Used With: All Units
Factory Preset: 35ºF
Possible Values: 25 to 40ºF
Used With: Units w/DX Cooling
Factory Preset: 30ºF
Possible Values: 25 to 35ºF
Used With: All Units
Factory Preset: DISABLED
Possible Values: DISABLED, ENABLED
Used With: All Units
Used With: VV/CVDA Units w/Cooling
and Heat Installed
Factory Preset: NONE
Possible Values: NONE, ZONE, OA
SETUP Menu
57