Trane S*HF*20-75 Troubleshooting Manual page 82

Commercial single zone rooftop air conditioner or commercial rooftop air handlers, with variable air volume (vvda/vvzt) controls or constant air volume (cvda/cvzt) controls intellipak i series; intellipak ii series;
Table of Contents

Advertisement

SETUP Menu
Actuator Setup
Direct/Reverse Act
• Press Next/Previous keys to navigate.
Actuator Setup
Max Stroke Time
• Press Next/Previous keys to navigate.
Actuator Setup
Min Voltage
• Press Next/Previous keys to navigate.
Actuator Setup
Max Voltage
• Press Next/Previous keys to navigate.
Actuator Setup
Direct/Reverse Act
• Press Next/Previous keys to navigate.
Actuator Setup
Max Stroke Time
• Press Next/Previous keys to navigate.
Actuator Setup
Min Voltage
• Press Next/Previous keys to navigate.
82
OR
Cond Fan VFD Ckt 2
DIRECT ACTING
Modulating Gas Heat
Modulating Gas Heat
2.0 VDC
Modulating Gas Heat
Modulating Gas Heat
DIRECT ACTING
Exh Bypass Damper
Exh Bypass Damper
2.0 VDC
Used With: Units w/DX Cooling, w/
Water-Cooled Condensers
Factory Preset: DIRECT
Possible Values: DIRECT, REVERSE
Used With: All Rooftop Units and Air
Handlers when Modulating Gas is
90 Sec
installed
Factory Presets: 90 Sec
Possible Values: 1 to 255 Sec
Used With: All Rooftop Units and Air
Handlers when Modulating Gas is
installed
Factory Presets: 2 VDC
Possible Values: 0 to 10.0 VDC
Used With: All Rooftop Units and Air
Handlers when Modulating Gas is
10 VDC
installed
Factory Presets: 10 VDC
Possible Values: 0 to 10.0 VDC
Used With: All Rooftop Units and Air
Handlers Modulating Gas is installed
Factory Presets: Direct Acting
Possible Values: Direct Acting, Reverse
Acting
Used With: All IntelliPak II units with
Energy Recovery installed.
60 Sec
Factory Preset: 60 Sec
Possible Values: 1 to 255 Sec
Used With: All IntelliPak II units with
Energy Recovery installed.
Factory Preset: 2.0 VDC
Possible Values: 0 to 10.0 VDC
RT-SVP07B-EN