If Remote Panel Mode Input Not Present:
System Mode: AUTO Supply Fan Mode: AUTO
• Press Next/Previous keys to navigate.
Reduce Multi-Unit Startup Power Demand
After Power-Up, Delay Unit Start
• Press Next/Previous keys to navigate.
Single Zone VAV Econ Control:
Single Zone VAV Heat Control:
• Press Next/Previous keys to navigate.
Daytime Warmup Function:
• Press Next/Previous keys to navigate.
Morning Warmup Function:
Morning Warmup Type:
• Press Next/Previous keys to navigate.
Supply Air Tempering Function:
Warm Up Outside Air Used For Ventilation
• Press Next/Previous keys to navigate.
RT-SVP07B-EN
0 Sec
ENABLED
DISABLED
ENABLED
ENABLED
FULL CAPACITY
ENABLED
Used With:
System Mode: All Units
Supply Fan Mode: CV SZVAV
Factory Presets:
System: AUTO
Supply Fan: AUTO
Possible Values:
System: OFF, AUTO
Supply Fan: ON, AUTO
Used With: All units.
Factory Presets: 0 Sec
Possible Values: 0 to 255 Sec
Used With: SZVAV Units
Factory Presets:
Econ: ENABLED
Heat: DISABLED
Possible Values:
ENABLED, DISABLED
Used With: VV/CVDA Units w/Heat
Installed
Factory Presets: ENABLED
Possible Values: ENABLED, DISABLED
Used With: Units w/Heat Installed
Factory Presets:
Function: ENABLED
Type: CYCLING CAPACITY
Possible Values:
Function: ENABLED, DISABLED
Type: FULL CAPACITY, CYCLING CAP.
Used With: VV/CVDA Units w/
Modulating Heat (w/Electric Heat if
IPakII), or CVZT Units w/Staged Heat
Installed.
Factory Preset: ENABLED
Possible Values: ENABLED, DISABLED
SETUP Menu
55