SETUP Menu
SENSOR SOURCE SELECTIONS SUBMENU SCREENS
Sensor Source Selections Submenu
Press ENTER to Review or Adjust
• Press the Next key to skip this Submenu.
For Daytime Warmup Temp Crtl, Use sensor
Connected to: RTM ZONE TEMP INPUT
• Press Next/Previous keys to navigate.
For Unoccupied Zone Temp Ctrl, Use Sensor
Connected To:
• Press Next/Previous keys to navigate.
For Unoccupied Zone Temp Ctrl, Use Sensor
Connected To:
• Press Next/Previous keys to navigate.
For Morning Warmup Temp Ctrl, Use Sensor
Connected To: RTM ZONE TEMP INPUT
• Press Next/Previous keys to navigate.
For Space Humidity Control, Use Sensor
Connected To:
• Press Next/Previous keys to navigate.
62
RTM ZONE TEMP INPUT
RTM ZONE TEMP INPUT
RTM SPACE HUMIDITY INPUT
Used With: All Units.
Used With: Units w/DWU ENABLED
Factory Preset: RTM ZONE TEMP INPUT
Possible Values:
RTM ZONE TEMP INPUT
NSB PANEL TEMP SENSOR INPUT
RTM AUX TEMP INPUT
HEAT MODULE AUX TEMP INPUT
ECEM RETURN AIR TEMP INPUT
Used With: All CV or SZVAV Unit, or
VAV w/DWU Installed
Factory Preset: RTM ZONE TEMP INPUT
Possible Values:
[See "DWU Source Selection" Above]
Used With: All Units
Factory Preset: RTM ZONE TEMP INPUT
Possible Values:
[See "DWU Source Selection" Above]
Used With: Units w/MWU ENABLED
Factory Preset: RTM ZONE TEMP INPUT
Possible Values:
[See "DWU Source Selection" Above]
Used With: Units w/Dehumidification or
Humidification Options
Factory Preset:
RTM SPACE HUMID INPUT
Possible Values:
RTM SPACE HUMIDITY INPUT
ECEM RA HUMIDITY INPUT
RT-SVP07B-EN