Trane S*HF*20-75 Troubleshooting Manual page 63

Commercial single zone rooftop air conditioner or commercial rooftop air handlers, with variable air volume (vvda/vvzt) controls or constant air volume (cvda/cvzt) controls intellipak i series; intellipak ii series;
Table of Contents

Advertisement

For Dehumid OVRD Zone Temp, Use Sensor
Connected To:
• Press Next/Previous keys to navigate.
For Zone Reset Function, Use Sensor
Connected To:
• Press Next/Previous keys to navigate.
For Rapid Restart Function, Use Sensor
Connected To:
• Press Next/Previous keys to navigate.
Monitor Specific Temp Input, Use Sensor
Connected To:
• Press Next/Previous keys to navigate.
End of Submenu (NEXT) to Enter SETUP
• Press Next/Previous keys to navigate.
OUTSIDE AIR VENTILATION SETUP SUBMENU SCREENS
Outside Air Ventilation Setup Submenu
Press ENTER to Review or Adjust
• Press the Next key to skip this Submenu.
Demand Controlled Ventilation:
DCV Setpoint Modified By Space CO2 Level
• Press Next/Previous keys to navigate.
RT-SVP07B-EN
RTM ZONE TEMP INPUT
RTM ZONE TEMP INPUT
RTM ZONE TEMP INPUT
RTM ZONE TEMP INPUT
ENABLED
Used With: Units w/Dehumid. Option
Factory Preset: RTM ZONE TEMP INPUT
Possible Values:
[See "DWU Source Selection" Above]
Used With: All Units
Factory Preset: RTM ZONE TEMP INPUT
Possible Values:
[See "DWU Source Selection" Above]
Used With: Units w/Rapid Restart
Factory Preset: RTM ZONE TEMP INPUT
Possible Values:
[See "DWU Source Selection" Above]
Used With: All Units
Factory Preset: RTM ZONE TEMP INPUT
Possible Values:
[See "DWU Source Selection" Above]
Used With: Units w/Fresh Air Option
Used With: Units w/ Fresh Air
Measurement (VCM) w/DCV or OA
Damper Min Position w/DCV Installed
Factory Preset: DISABLED
Possible Values: ENABLED, DISABLED
Bottom Field:
If ENABLED: "DCV Setpoint Modified
By Space CO
Level"
2
If DISABLED: (blank)
SETUP Menu
63