Table 2. Factory Presets List (continued)(Note: Listed Items availability is dependent on unit configuration.
Adjustable Function
Supply Air Low Limit
VCM Preheat Actuate Temp
Design Min CO
(DCV)
2
2
DCV Min CO
Design Min OA Flow (DCV)
DCV Min OA Flow
DCV Min OA Flow Deadband
Min OA Flow w\ VCM
Min OA Flow Deadband
Design Min OA Damper Position (DCV)
DCV Min OA Damper Position
OA Damper Min Position (non-DCV)
OAD Min Position w/IGV/VFD at 0%
OAD Min Position w/IGV/VFD at 50%
OAD Min Position w/IGV/VFD at 100%
OAD Min Position (Default)
Supply Air Pressure
Supply Air Pressure High Limit
Supply Air Pressure Deadband
Max Return Plenum Pressure
Return Plenum Pressure Deadband
Space Pressure - Setpoint
Space Pressure - Deadband
Space Pressure Low Limit
Exhaust Enable Point
Exhaust Inhibit Point
Low Ambient Comp. Lockout (Standard Units)
Low Ambient Comp. Lockout (Low Ambient Units)
Standby Freeze Avoidance
Recovery Frost Avoidance Setpoint
Setpoint Source Selection For...
Supply Air Temp Cooling
Supply Air Temp Heating
Occupied Zone Cooling
Occupied Zone Heating
Unoccupied Zone Cooling
Unoccupied Zone Heating
Morning Warm-Up
Economizer Dry Bulb Enable
Outside Damper Minimum Position
Occupied Dehumidification
Unoccupied Dehumidification
Supply Air Reheat
RT-SVP07B-EN
Factory Preset
Changed To
50 F
___________
35 F
___________
1000 PPM
___________
1
2
800
/400
PPM
___________
220 CCFM
___________
67 CCFM
___________
5 CCFM
___________
Set per unit size
___________
Set per unit size
___________
15 %
___________
5 %
___________
15 %
___________
25%
___________
20%
___________
15%
___________
15%
___________
2.0 IWC
___________
4.0 IWC
___________
0.5 IWC
___________
0.8 IWC
___________
0.1 IWC
___________
0.08 IWC
___________
.04 IWC
___________
-0.2 IWC
___________
25 %
___________
DISABLE
___________
50 F
___________
0 F
___________
0 %
___________
27 F
___________
Hi Default
___________
Hi Default
___________
Hi Default
___________
Hi Default
___________
Hi Default
___________
Hi Default
___________
Hi Default
___________
Hi Default
___________
Hi Default
___________
Hi Default
___________
Hi Default
___________
Hi Default
___________
General Status Display
To adjust
press...
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
23