SETUP Menu
SZVAV Cooling Control Gains
Proportional 6.0 %/F Reset Time 1200 Sec
Note: This screen must be changed on field replacement of the
RTM Module.
• Press Next/Previous keys to navigate.
SZVAV Heating Control Gains
Proportional 8.0 %/F Reset Time 1200 Sec
Note: This screen must be changed on field replacement of the
RTM Module.
• Press Next/Previous keys to navigate.
Zone Control Occupied Heating Gains
Proportional 30.0 %/F Reset Time 1800 Sec
Note: This screen must be changed on field replacement of the
RTM Module.
Table 6. Proportional Parameter - Staged Heat
Staged Heat
Product
Type
IPak I
Gas
IPak I
Electric
IPak II
Gas
IPak II
Electric 90 kw
IPak II
Electric 140 kw
IPak II
Electric 265 kw
IPak II
Electric 300 kw
• Press Next/Previous keys to navigate.
Rapid DX Interstage Timing:
Note: This screen must be changed on field replacement of the
RTM Module.
• Press Next/Previous keys to navigate.
End of Submenu (NEXT) to Enter SETUP
• Press Next/Previous keys to navigate.
84
Proportional
No of Stages
Gain
2
30.0
3
45.0
2
30.0
3
45.0
4
60.0
5
75.0
5
75.0
Used With: All IntelliPak units with
SZVAV Installed.
Factory Preset:
Prop: 6.0
Reset: 1200
Possible Values:
Prop: 0.2 - 50
Reset: 90 - 3600, DISABLED
Used With: All IntelliPak units with
SZVAV Installed.
Factory Preset:
Prop: 8.0
Reset: 1200
Possible Values:
Prop: 0.2 - 50
Reset: 90 - 3600, DISABLED
Used With: All IntelliPak units with
Staged Heat Installed.
Range: 2.0 - 200
Possible Values:
[See
"Table 6. Proportional Parameter -
Staged Heat"
assignments.]
Used With: All IntelliPak units w/
30 Sec
Dehumidification or Rapid Restart.
Factory Presets: Range: 30
Possible Values: 15 - 50
on page 84 for