CONTROLLING SENSOR STATUS SUBMENU SCREENS
Controlling Sensor Status Submenu
Press ENTER to View Data in This Submenu
• Press the Next key to skip this Submenu.
Active Supply Air Temp Sensv Input From
BAS/NETWORK
• Press Next/Previous keys to navigate.
Active Daytime WU Temp Sensor Input From
RTM ZONE TEMP INPUT
• Press Next/Previous keys to navigate.
Active Occ Zone Temp Sensor Input From
RTM ZONE TEMP INPUT is
• Press Next/Previous keys to navigate.
Active Unocc Zone Temp Sensor Input From
RTM ZONE TEMP INPUT is
• Press Next/Previous keys to navigate.
Active Morning WU Temp Sensor Input From
RTM ZONE TEMP INPUT
• Press Next/Previous keys to navigate.
Active Space Humidity Sensor Input From
RTM SPACE HUMIDITY INPUT
• Press Next/Previous keys to navigate.
RT-SVP07B-EN
is
50.0°F
is
82.0°F
75.0°F
75.0°F
is
82.0°F
is
Used With: All Units
Used With: All Units
Possible Values:
RTM Supply Air Temp Input
BAS/Network
Used With: Units w/DWU ENABLED
Possible Values:
RTM ZONE TEMP INPUT
NSB PANEL TEMP SENSOR INPUT
RTM AUX TEMP INPUT
HEAT MODULE AUX TEMP INPUT
ECEM RETURN AIR TEMP INPUT BAS/
NETWORK SENSOR
Range: -40 to 200ºF
Used With: CV or SZVAV Units
Possible Values:
[See "Possible Values:" Above]
Used With: All Units
Possible Values:
[See "Possible Values:" Above]
Used With: Units w/MWU ENABLED
Possible Values:
[See "Possible Values:" Above]
Used With: Units w/Dehumid. or Humid.
Option
55%
Possible Values:
RTM SPACE HUMIDITY INPUT
ECEM RA HUMIDITY INPUT
BAS/NETWORK
Range: 10 to 90%
STATUS Menu
45