Trane S*HF*20-75 Troubleshooting Manual page 80

Commercial single zone rooftop air conditioner or commercial rooftop air handlers, with variable air volume (vvda/vvzt) controls or constant air volume (cvda/cvzt) controls intellipak i series; intellipak ii series;
Table of Contents

Advertisement

SETUP Menu
Note: Only one of the following two screens will be shown based
on condenser type.
Actuator Setup
Min Voltage
Actuator Setup
Min Voltage
• Press Next/Previous keys to navigate.
Note: Only one of the following two screens will be shown based
on condenser type.
Actuator Setup
Max Voltage
Actuator Setup
Max Voltage
• Press Next/Previous keys to navigate.
Note: Only one of the following two screens will be shown based
on condenser type.
Actuator Setup
Direct/Reverse Act
Actuator Setup
Direct/Reverse Act
• Press Next/Previous keys to navigate.
80
Num 1 Low Ambient
2.0 VDC
OR
Cond Fan VFD Ckt 1
0.0 VDC
Num 1 Low Ambient
10.0 VDC
OR
Cond Fan VFD Ckt 1
10.0 VDC
Num 1 Low Ambient
DIRECT ACTING
OR
Cond Fan VFD Ckt 1
DIRECT ACTING
Used With: Units w/DX Cooling, w/Air-
Cooled Condensers
Factory Presets: 2.0 VDC
Possible Values: 0 to 10.0 VDC
Used With: Units w/DX Cooling, w/
Water-Cooled Condensers
Factory Preset: 0 VDC
Possible Values: 0 to 10.0 VDC
Used With: Units w/DX Cooling, w/Air-
Cooled Condensers
Factory Presets: 10.0 VDC
Possible Values: 0 to 10.0 VDC
Used With: Units w/DX Cooling, w/
Water-Cooled Condensers
Factory Preset: 10.0 VDC
Possible Values: 0 to 10.0 VDC
Used With: Units w/DX Cooling, w/Air-
Cooled Condensers
Factory Presets: Direct Acting
Possible Values: Direct Acting, Reverse
Acting
Used With: Units w/DX Cooling, w/
Water-Cooled Condensers
Factory Preset: DIRECT
Possible Values: DIRECT, REVERSE