SETPOINT Menu
Default Design Min OA Flow Stp: 350 CCFM
Default DCV Min OA Flow Setpt:
• Press Next/Previous keys to navigate.
Demand Controlled Ventilation
Min OA Flow deadband:
• Press Next/Previous keys to navigate.
Note: The following screen is only shown if DCV is disabled.
Default Min OA Flow Setpoint:
Min OA Flow Deadband:
Table 7. Max Unit Airflows
Max Airflow
Capacity
Product
(Tons)
IPak
20 to 25
IPak
30
IPak
40
IPak
50 to 55
IPak
60 to 75
IPak
90 to 130
IPak II
90 to 105
IPak II
120 to 150
• Press Next/Previous keys to navigate.
90
OR
Deadband
Range
Range
(CFM)
(CFM)
0 to 14000
500 to 2000
0 to 17000
500 to 2000
0 to 22000
500 to 2000
0 to 28000
500 to 2000
0 to 33000
700 to 2000
0 to 46000
1000 to 2000
0 to 45000
500 to 2000
0 to 58500
500 to 2000
Used With: Units w/Fresh Air
Measurement (VCM) w/DCV
150 CCFM
Factory Preset: 220 CCFM
Ovrd to 112 CCFM for 90 and 105 Ton
Ovrd to 146 CCFM for 120 and 130 Ton
Possible Values:
Design Min OA Flow: 0 to 585 CCFM
DCV Min OA Flow: 0 to 585 CCFM
Used With: Units w/Fresh Air
Measurement (VCM) w/DCV
5 CCFM
Factory Presets: 5 CCFM
Possible Values: 5 to 20 CCFM
Used With: Units w/Fresh Air
40 CCFM
Measurement (VCM) w/o DCV
5.0 CCFM
Factory Presets:
Setpoint: 40 CCFM
Deadband: 5 CCFM
Possible Values:
[See
"Table 7. Max Unit
assignments.]
Airflows" for
RT-SVP07B-EN