Toshiba H7 Operation Manuals page 84

Adjustable speed drive
Hide thumbs Also See for H7:
Table of Contents

Advertisement

F166
OUT7 Off Delay
Program
Terminal Selection Parameters
OUT7
This parameter delays the opening of the OUT7 output terminals by the
programmed value (see waveforms at F160).
The delay may be increased to allow the devices that are connected to OUT7 to
respond.
Motor #2 Base Frequency
Program
Motor Parameters
The Motor #2 Base Frequency setting is the frequency at which the output
voltage of the ASD reaches its maximum setting. The #2 Maximum Output
Voltage is set at F171.
This parameter is used only when the parameters for motor set #2 are
configured and selected. Motor set #2 may be selected by a properly configured
input terminal.
For proper motor operation, the Base Frequency should be set for the name-
plated frequency of the motor.
Motor #2 Max Output Voltage
Program
Motor Parameters
The Motor #2 Maximum Output Voltage is the Motor #2 output voltage at
the Base Frequency (F170). Regardless of the programmed value, the output
voltage cannot be higher than the input voltage.
The actual output voltage will be influenced by the input voltage of the ASD
and the Supply Voltage Compensation setting (F307).
This parameter is used only when the parameters for motor set #2 are
configured and selected. Motor set #2 may be selected by a properly configured
input terminal.
Motor #2 Torque Boost
Program
Motor Parameters
The Motor #2 Torque Boost function is used to increase the low frequency
torque for high inertia loads by increasing the output voltage at frequencies
below ½ of the #2 Base Frequency setting (F170).
See parameter
F016
(Motor #1 Torque Boost) for an explanation of torque
boost.
This parameter is used only when the parameters for motor set #2 are
configured and selected. Motor set #2 may be selected by a properly configured
input terminal.
H7 ASD Operation Manual
Output Terminal Delays
Motor Set #2
Motor Set #2
Motor Set #2
Direct Access Number — F166
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
Direct Access Number — F170
Parameter Type — Numerical
Factory Default — 60.0
Changeable During Run — Yes
Minimum — 25.0
Maximum — 400.0
Units — Hz
Direct Access Number — F171
Parameter Type — Numerical
Factory Default — (drive dependent)
Changeable During Run — Yes
Minimum — 0.0
Maximum — 600.0
Units — Volts
Direct Access Number — F172
Parameter Type — Numerical
Factory Default — (drive dependent)
Changeable During Run — Yes
Minimum — 0.0
Maximum — 30.0
Units — %
F172
77