F675
Analog 2 Terminal Adjustment
Program
Meter Terminal Adjustment Parameters
This parameter adjusts the coefficient of the circuit to obtain an output that
corresponds with a known input.
This function is used in the calibration of external signal measuring devices
(DVM, counters, etc.).
FP Terminal Setting
Program
Terminal Selection Parameters
This parameter commands the multifunction programmable FP terminal to
monitor the value of 1 of 31 possible system functions. As the monitored
function changes in magnitude or frequency, the pulse count of the FP output
pulse train changes in direct proportion to changes in the monitored function.
As the monitored value goes up so does the pulse count of the FP output.
Note: The duty cycle of the output pulse train remains at 65 ±5.0 µS.
Possible assignments for this output terminal are listed in
FP Terminal Adjustment
Program
Terminal Selection Parameters
This parameter sets the full-scale reading of the FP Terminal. The full-scale
reading of the monitored variable selected in
Display Units for Voltage and Current
Program
Utility Parameters
This parameter sets the unit of measurement for current and voltage values
displayed on the EOI.
Settings:
%
V/A
Hz Per User-defined Unit
Program
Utility Parameters
This parameter allows the user to input a quantity to be displayed on the EOI
that is proportional to the output frequency of the drive.
This feature is useful when the output of a process is moved along at a rate that
is proportional to the output frequency of the drive.
H7 ASD Operation Manual
Analog 2
FP
Table 5 on pg.
FP
F676
may be set here.
Display Units
Display Units
Direct Access Number — F675
Parameter Type — Numerical
Factory Default — 512
Changeable During Run — Yes
Minimum — 1
Maximum — 1280
Direct Access Number — F676
Parameter Type — Selection List
Factory Default — Output Frequency
Changeable During Run — Yes
50.
Direct Access Number — F677
Parameter Type — Numerical
Factory Default — 3.840
Changeable During Run — Yes
Minimum — 1.000
Maximum — 43.200
Units — kHz
Direct Access Number — F701
Parameter Type — Selection List
Factory Default — %
Changeable During Run — Yes
Direct Access Number — F702
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 200.0
Units — Hz/UDU
F702
165