F023
Preset Speed #6
Program
Pattern Run Control
⇒
This parameter assigns an output frequency to binary number 0110 and is
identified as Preset Speed #6. The binary number is applied to S1 – S4 of the
Control Terminal Strip to output the Preset Speed (see
information on this parameter).
Preset Speed #7
Program
⇒
Pattern Run Control
This parameter assigns an output frequency to binary number 0111 and is
identified as Preset Speed #7. The binary number is applied to S1 – S4 of the
Control Terminal Strip to output the Preset Speed (see
information on this parameter).
Low Speed Signal Output Frequency
Program
⇒
Terminal Selection Parameters
The Low Speed Signal Output Frequency parameter sets a frequency
threshold that activates the assigned output terminal so long as the ASD output
is at or below this setting (see
assignments).
Speed Reach Frequency
Program
Terminal Selection Parameters
⇒
The Speed Reach Frequency sets a frequency threshold that, when reached or
is within the bandwidth specified by parameter F102, will provide a signal at an
output terminal that can close an appropriately configured output contact (see
Table 7 on pg. 72
for the available output assignments).
H7 ASD Operation Manual
Preset Speeds
6
⇒
⇒
F018
⇒
Preset Speeds
⇒
7
F018
⇒
Reach Settings
Table 7 on pg. 72
for the available output
Reach Settings
⇒
Direct Access Number — F023
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
for further
Minimum — Lower Limit (F013)
Maximum — Upper Limit (F012)
Units — Hz
Direct Access Number — F024
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
for further
Minimum — Lower Limit (F013)
Maximum — Upper Limit (F012)
Units — Hz
Direct Access Number — F100
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq. (F011)
Units — Hz
Direct Access Number — F101
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq. (F011)
Units — Hz
F101