Toshiba H7 Operation Manuals page 136

Adjustable speed drive
Hide thumbs Also See for H7:
Table of Contents

Advertisement

F441
Driving Torque Limit #1
Program
Torque Setting Parameters
Settings
This parameter provides a value for the Power Running Torque Limit #1
setting if Setting is selected at F440. This value provides the positive torque
upper limit for the #1 motor.
Regeneration Torque Limit #1
Program
Torque Setting Parameters
This parameter determines the source of the Regenerative Torque Limit
control signal. If Setting is selected, the value set at
parameter.
Settings:
VI/II
RR
RX
RX2 (option)
Setting
Regeneration Torque Limit Setting #1
Program
Torque Setting Parameters
Manual Settings
This parameter provides a value to be used as the Regeneration Torque Limit
#1 if Setting is selected at F442.
Driving Torque Limit #2
Program
Torque Setting Parameters
Settings
This parameter is used to set the positive torque upper limit for the #2 motor
profile when multiple motors are controlled by a single drive or when a single
motor is to be controlled by multiple profiles.
H7 ASD Operation Manual
Manual Torque Limit
Torque Limit Settings
F443
is used for this
Torque Limit Settings
Manual Torque Limit
Direct Access Number — F441
Parameter Type — Numerical
Factory Default — 250.0
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0
Units — %
Direct Access Number — F442
Parameter Type — Selection List
Factory Default — Setting
Changeable During Run — Yes
Direct Access Number — F443
Parameter Type — Numerical
Factory Default — 250.0
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0
Units — %
Direct Access Number — F444
Parameter Type — Numerical
Factory Default — 250.0
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0
Units — %
F444
129