F134
Output #5 Terminal Assignment
Program
Terminal Selection Parameters
⇒
Assignment
⇒
5
This parameter sets the functionality of the output #5 terminals to 1 of the 60
possible functions that are listed in
The on and off delay times of the #5 terminals may be adjusted to provide more
response time to the device that is connected to the output terminals.
In addition, the output terminals must be specified as Normally Open or
Normally Closed.
Output #6 Terminal Assignment
Program
⇒
Terminal Selection Parameters
Assignment
⇒
6
This parameter sets the functionality of the output #6 terminals to 1 of the 60
possible functions that are listed in
The on and off delay times of the #6 terminals may be adjusted to provide more
response time to the device that is connected to the output terminals.
In addition, the output terminals must be specified as Normally Open or
Normally Closed.
Output #7 Terminal Assignment
Program
Terminal Selection Parameters
⇒
Assignment
⇒
7
This parameter sets the functionality of the output #7 terminals to 1 of the 60
possible functions that are listed in
The on and off delay times of the #7 terminals may be adjusted to provide more
response time to the device that is connected to the output terminals.
In addition, the output terminals must be specified as Normally Open or
Normally Closed.
F Input Terminal Delay
Program
⇒
Terminal Selection Parameters
F
This parameter delays the response of the ASD to any change in the F terminal
input by the programmed value.
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
H7 ASD Operation Manual
Output Terminal
⇒
Table 7 on pg.
72.
⇒
Output Terminal
Table 7 on pg.
72.
Output Terminal
⇒
Table 7 on pg.
72.
⇒
Input Terminal Delays
Direct Access Number — F134
Parameter Type — Selection List
Factory Default — UL
Changeable During Run — No
Direct Access Number — F135
Parameter Type — Selection List
Factory Default — RCH (Specified
Speed)
Changeable During Run — No
Direct Access Number — F136
Parameter Type — Selection List
Factory Default — Overcurrent
Prealarm
Changeable During Run — No
Direct Access Number — F140
⇒
Parameter Type — Numerical
Factory Default — 8.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
F140
71