F598
Pattern Run #14 Run-Time Setting
Program
Pattern Run Control Parameters
This parameter sets the run-time value for the #14 Preset Speed mode when
used as part of a Pattern Run.
Pattern Run #15 Run-Time Setting
Program
Pattern Run Control Parameters
This parameter sets the run-time value for the #15 Preset Speed mode when
used as part of a Pattern Run.
Electronic Thermal Protection #1
Program
Motor Parameters
The Motor #1 Electronic Thermal Protection parameter specifies the motor
overload current level for motor set #1. This value is entered as either a
percentage of the full load rating of the ASD or as the FLA of the motor.
The unit of measurement for this parameter may be set to Amps or it may be set
as a percentage of the ASD rating. The name-plated FLA of the motor may be
entered directly when Amps is selected as the unit of measurement (see
change the display unit).
Electronic Thermal Protection settings (#1 – #4) will be displayed in Amps if
the EOI display units are set to V/A rather than %.
Overcurrent Stall Level
Program
Protection Parameters
This parameter specifies the output current level at which the output frequency
is reduced in an attempt to prevent a trip. The overcurrent level is entered as a
percentage of the maximum rating of the drive.
154
Preset Speeds
Preset Speeds
Motor Set #1
Stall
Direct Access Number — F598
14
Parameter Type — Numerical
Factory Default — 5
Changeable During Run — No
Minimum — 1
Maximum — 8000
Units — Seconds
Direct Access Number — F599
15
Parameter Type — Numerical
Factory Default — 5
Changeable During Run — No
Minimum — 1
Maximum — 8000
Units — Seconds
Direct Access Number — F600
Parameter Type — Numerical
Factory Default — 100.0
Changeable During Run — Yes
Minimum — 10.0
Maximum — 100.0
F701
to
Units — %
Direct Access Number — F601
Parameter Type — Numerical
Factory Default — (drive dependent)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 200.0
Units — %