F125
Input #15 Terminal Assignment
Program
Terminal Selection Parameters
⇒
Assignment
⇒
S15
This parameter selects the functionality of the #15 input terminal.
Note: The S15 input terminal may be used without the ASD-Multicom option
board.
Without the ASD-Multicom option board the S15 terminal assignment
information will be stored in volatile memory. The terminal assignment
information will be lost if the system is powered down or reset.
In addition, the input terminal must be specified as Normally Open or
Normally Closed.
This parameter sets the programmable terminal #15 to 1 of the 68 possible
functions that are listed in
Table 6 on pg.
Input #16 Terminal Assignment
Program
⇒
Terminal Selection Parameters
Assignment
⇒
S16
This parameter selects the functionality of the #16 input terminal.
Note: The S16 input terminal may be used without the ASD-Multicom option
board.
Without the ASD-Multicom option board the S16 terminal assignment
information will be stored in volatile memory. The terminal assignment
information will be lost if the system is powered down or reset.
In addition, the input terminal must be specified as Normally Open or
Normally Closed.
This parameter sets the programmable terminal #16 to 1 of the 68 possible
functions that are listed in
Table 6 on pg.
66
Input Terminal
⇒
67.
⇒
Input Terminal
67.
Direct Access Number — F125
Parameter Type — Selection List
Factory Default — Unassigned
Changeable During Run — No
Direct Access Number — F126
Parameter Type — Selection List
Factory Default — Unassigned
Changeable During Run — No
H7 ASD Operation Manual
F126