Toshiba H7 Operation Manuals page 121

Adjustable speed drive
Hide thumbs Also See for H7:
Table of Contents

Advertisement

F324
Drooping Output Filter
Program
Feedback Parameters
Contact Toshiba's Marketing Department for information on this parameter.
Load Inertia (Acc/Dec Torque)
Program
Feedback Parameters
This parameter is used for calculating accel/decel torque when compensating
for load inertia while operating in the Drooping Control mode.
Load Torque Filter (Acc/Dec Torque)
Program
Feedback Parameters
This parameter is used to set the response sensitivity when calculating the accel/
decel torque. This setting applies to load inertia compensation while operating
in the Drooping Control mode.
This parameter should be gradually adjusted to provide smoother Drooping
Control operation while operating with heavy loads.
Drooping Reference
Program
Feedback Parameters
Reference
This parameter sets the method to be used in determining the output torque
while operating in the Drooping Control mode.
Settings:
Total Torque Calculated by the Detection Current.
Torque without Acc/Dec Torque Calculated by Detection Current.
Total Torque Calculated by the Command Current.
Torque without Acc/Dec Torque Calculated by the Command Current.
On-Trip Powerline Switching
Program
Terminal Selection Parameters
This parameter Enables/Disables the On Trip Powerline Switching feature.
When enabled, the system is instructed to discontinue using the output of the
drive and to switch to the commercial power in the event of a trip.
114
Drooping Control
Drooping Control
Load Inertia
Drooping Control
Load Inertia
Drooping Control
Drooping
Line Power Switching
Direct Access Number — F324
Parameter Type — Numerical
Factory Default — 100.0
Changeable During Run — Yes
Minimum — 0.1
Maximum — 200.0
Direct Access Number — F325
Parameter Type — Numerical
Factory Default — 1.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 1000.0
Direct Access Number — F326
Parameter Type — Numerical
Factory Default — 200.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 200.0
Direct Access Number — F327
Parameter Type — Selection List
Factory Default — Total torque
calculated by the detection current
Changeable During Run — Yes
Direct Access Number — F354
Parameter Type — Check Box
Factory Default — Disabled
Changeable During Run — No
H7 ASD Operation Manual
F354

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents