F453
Stall Prevention During Regeneration
Program
Protection Parameters
⇒
Regeneration
This parameter Enables/Disables the Overvoltage Stall (F305) and the
Overcurrent Stall (F017) function during regeneration only. Application-
specific conditions may occur that warrant disabling the Stall function during
regeneration.
Settings:
With Stall Prevention
Without Stall Prevention
Current Differential Gain
Program
⇒
Special Control Parameters
Current Differential Gain
This parameter determines the degree that the current differential function
affects the output signal. The larger the value entered here, the more
pronounced the Current Differential Gain.
VI/II Bias Adjust
Program
⇒
Frequency Setting Parameters
Setpoints
VI/II
Bias
⇒
⇒
This parameter is used to fine-tune the bias of the VI/II input terminals.
Note: See note on
pg. 33
for further information on the VI/II terminal.
This setting may be used to ensure that the zero level of the input source (pot,
pressure transducer, flow meter, etc.) is also the zero level setting of the ASD
system.
This is accomplished by setting the input source to zero and either increasing or
decreasing this setting to provide an output of zero from the ASD.
VI/II Gain Adjust
Program
⇒
Frequency Setting Parameters
Setpoints
⇒
VI/II
⇒
Gain
This parameter is used to fine tune the gain of the VI/II input terminals.
Note: See note on
pg. 33
for further information on the VI/II terminal.
This setting may be used to ensure that the 100% level of the input source (pot,
pressure transducer, flow meter, etc.) is also the 100% level setting of the ASD
system.
This is accomplished by setting the input source to 100% and either increasing
or decreasing this setting to provide an output of 100% from the ASD.
132
Stall
Stall Prevention During
⇒
⇒
⇒
Special Parameters
⇒
Speed Reference
⇒
Speed Reference
Direct Access Number — F453
Parameter Type — Selection List
Factory Default — With Stall
Prevention.
Changeable During Run — Yes
Direct Access Number — F454
⇒
Parameter Type — Numerical
Factory Default — 1.23
Changeable During Run — Yes
Direct Access Number — F470
Parameter Type — Numerical
Factory Default — 100
Changeable During Run — Yes
Minimum — 0.0
Maximum — 255
Direct Access Number — F471
Parameter Type — Numerical
Factory Default — 50
Changeable During Run — Yes
Minimum — 0.0
Maximum — 255
H7 ASD Operation Manual
F471