F223
RX2 Speed Reference Setpoint #1 (frequency)
Program
Frequency Setting Parameters
Setpoints
RX2
This parameter is used to set the direction, gain, and bias of the RX2 input
terminal when this terminal is used as the control input while operating in the
Speed Control mode.
See
F222
for further information on this setting.
This parameter sets RX2 Speed Reference Setpoint #1 (frequency) and is the
frequency that is associated with the setting of F222.
RX2 Speed Reference Setpoint #2 (%)
Program
Frequency Setting Parameters
Setpoints
RX2
This parameter is used to set the direction, gain, and bias of the RX2 input
terminal when this terminal is used as the control input while operating in the
Speed Control or the Torque Control mode.
See
F222
for further information on this setting.
This parameter sets the RX2 input level that represents RX2 Reference
Setpoint #2 (frequency) (direction/torque/frequency). This value is entered as
-100 to +100% of the -10 to +10 VDC RX2 input signal range.
RX2 Speed Reference Setpoint #2 (frequency)
Program
Frequency Setting Parameters
Setpoints
RX2
This parameter is used to set the direction, gain, and bias of the RX2 input
terminal when this terminal is used as the control input while operating in the
Speed Control mode.
See
F222
for further information on this setting.
This parameter sets RX2 Speed Reference Setpoint #2 (frequency) and is the
frequency that is associated with the setting of F224.
RX2 Torque Reference Setpoint #1 (%)
Program
Torque Setting Parameters
This parameter is used to set the direction, gain, and bias of the RX2 input
terminal when this terminal is used as the control input while operating in the
Torque Control mode.
This is accomplished by establishing an associated V/f output pattern for a
given RX2 input level and motor load.
See
F222
for further information on this setting.
This parameter sets RX2 Torque Reference Setpoint #1 (%) and is the output
torque value that is associated with the setting of F222. This value is entered as
-250 to +250% of the rated torque.
H7 ASD Operation Manual
Speed Reference
Speed Reference
Speed Reference
Setpoints
RX2
Direct Access Number — F223
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — -80.0
Maximum — +80.0
Units — Hz
Direct Access Number — F224
Parameter Type — Numerical
Factory Default — +100.0
Changeable During Run — Yes
Minimum — -100.0
Maximum — +100.0
Units — %
Direct Access Number — F225
Parameter Type — Numerical
Factory Default — +80.0
Changeable During Run — Yes
Minimum — -80.0
Maximum — +80.0
Units — Hz
Direct Access Number — F226
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — -250.0
Maximum — +250.0
Units — %